<Appendix 5. PID Block>

A5-3

IM 01C25T02-01E

Index

Parameter

Name

Default

(factory setting)

Write

Valid Range

Description

35

RCAS_OUT

0

Remote setpoint sent to a computer, etc.

36

ROUT_OUT

0

Remote control output value.

37

TRK_SCALE

100

0

1342

1

MAN

Upper and lower scale limits used to convert the output

tracking value (TRK_VAL) to non-dimensional.

38

TRK_IN_D

0

Switch for output tracking. See Section A5.12 for

details.

39

TRK_VAL

0

Output tracking value (TRK_VAL).

When MODE_BLK.actual = LO, the value scaled from

the TRK_VAL value is set in OUT.

40

FF_VAL

0

Feedforward input value.

The FF_VAL value is scaled to a value with the same

scale as for OUT, multiplied by the FF_GAIN value, and

then added to the output of the PID computation.

41

FF_SCALE

100

0

1342

1

MAN

Scale limits used for converting the FF_VAL value to a

non-dimensional value.

42

FF_GAIN

0

MAN

Gain for FF_VAL.

43

UPDATE_EVT

Same as that for an AI block.

44

BLOCK_ALM

Same as that for an AI block.

45

ALARM_SUM

Enable

Same as that for an AI block.

46

ACK_OPTION

0xFFFF

Same as that for an AI block.

47

ALARM_HYS

0.5%

0 to 50%

Hysteresis for alarm detection and resetting to prevent

each alarm from occurring and recovering repeatedly

within a short time.

48

HI_HI_PRI

0

0 to 15

Priority order of HI_HI_ALM alarm.

49

HI_HI_LIM

+INF

PV_SCALE

Setting for HI_HI_ALM alarm.

50

HI_PRI

0

0 to 15

Priority order of HI_ALM alarm.

51

HI_LIM

+INF

PV_SCALE

Setting for HI_ALM alarm.

52

LO_PRI

0

0 to 15

Priority order of LO_ALM alarm.

53

LO_LIM

-INF

PV_SCALE

Setting for LO_ALM alarm.

54

LO_LO_PRI

0

0 to 15

Priority order of LO_LO_ALM alarm.

55

LO_LO_LIM

-INF

PV_SCALE

Setting for LO_LO_ALM alarm.

56

DV_HI_PRI

0

0 to 15

Priority order of DV_HI_ALM alarm.

57

DV_HI_LIM

+INF

Setting for DV_HI_ALM alarm.

58

DV_LO_PRI

0

0 to 15

Priority order of DV_LO_ALM alarm.

59

DV_LO_LIM

-INF

Setting for DV_LO_ALM alarm.

60

HI_HI_ALM

Alarm that is generated when the PV value has

exceeded the HI_HI_LIM value and whose priority

order* is defined in HI_HI_PRI.

* Priority order: Only one alarm is generated at a time.

When two or more alarms occur at the same

time, the alarm having the highest priority order is

generated.

When the PV value has decreased below [HI_HI_

LIM - ALM_HYS], HI_HI_ALM is reset.

61

HI_ALM

As above

62

LO_ALM

As above

Reset when the PV value has increased above

[LO_LIM + ALM_HYS].

63

LO_LO_ALM

As above

64

DV_HI_ALM

Alarm that is generated when the value of [PV - SP] has

exceeded the DV_HI_LIM value. Other features are the

same as HI_HI_ALM.

65

DV_LO_ALM

Alarm that is generated when the value of [PV - SP] has

decreased below the DV_LO_LIM value. Other features

are the same as LO_LO_ALM.