A3.4.2 out processing, A3.4.2, A3-13 – Yokogawa EJX930A User Manual

Page 108

Advertising
background image

<Appendix 3. Input Selector (IS) Block>

A3-13

IM 01C25T02-01E

A3.4.2 OUT Processing

OUT is an output parameter used to send the value selected in the IS block to another function block.
The following describes OUT processing.

Table A3.3 Block Mode and Value

MODE

Value

O/S

· The previous value is output. (At startup, the initial value is

used).

· Writable (the operator may change the value.)

Man

A

u

t

o

Value specified by MIN_Good > the number of

valid inputs

· The previous value is output.

· Not writable

If there is no valid input
If the input status is “bad” or “uncertain” when

the value of OP_SELECT is anything other than

“0” (with the exception of the case where the

“Uncertain as good” bit in STATUS_OPTS is set)
If the value of OP_SELECT is greater than 8,

which is the maximum number of inputs

· Zero

· Not writable

If OP_SELECT is enabled

· The value of the selected input is output.

· Not writable

If the value is out of the SELECT_TYPE setting

range when the value of OP_SELECT is “0”

· The previous value is output.

· Not writable

If SELECT_TYPE is “First Good”

· The value of a valid input with the smallest input number is

output.

· Not writable

If SELECT_TYPE is “MINIMUM”

· The minimum value among the values of the valid inputs is

output.

· Not writable

If SELECT_TYPE is “MAXIMUM”

· The maximum value among the values of the valid inputs is

output.

· Not writable

If SELECT_TYPE is “MIDDLE”

(There is an even multiple number of valid inputs.)

· Because two inputs are positioned in the middle of the values

of even multiple valid inputs, the average of the values of

these two inputs is output.

· Not writable

If SELECT_TYPE is “MIDDLE”

(There is an odd multiple number of valid inputs.)

· The value of the input positioned in the middle of the values of

odd multiple valid inputs is output.

· Not writable

If SELECT_TYPE is “AVERAGE”

· The value obtained by dividing the added value of the values

of valid inputs by the number of these inputs is output.

· Not writable

If SELECT_TYPE is “Latched Good”

· The value of a valid input with the smallest input number is

output.

· Not writable

Table A3.4 Condition and Mode

Condition (Listed in priority sequence)

Mode

If the Actual is in O/S

O/S

If the “Uncertain if Man mode” bit in STATUS_OPTS is set and the Actual is in Man

Man

If the “Uncertain if Man mode” bit in STATUS_OPTS is not set and the Actual is in Man

Man

Values specified by MIN_Good > the number of valid inputs

Aute

If there is no valid input

Aute

If the input status is “bad” or “uncertain” when the value of OP_SELECT is anything other than “0”

(with the exception of the case where the “Uncertain as good” bit in STATUS_OPTS is set)

Aute

If the value of OP_SELECT is greater than 8, which is the maximum number of inputs

Aute

If OP_SELECT has selected IN whose status is “bad” or “uncertain”

(See the item “Transition of Sub-status in the Case Where OP_SELECT is Selected.”)

Aute

If the value is out of the SELECT_TYPE setting range when the value of OP_SELECT is “0”

Aute

Advertising