A3.4.3 status_opts, A3.5 list of input selector block parameters, A3.4.3 – Yokogawa EJX930A User Manual

Page 109: A3.5, A3-14

Advertising
background image

<Appendix 3. Input Selector (IS) Block>

A3-14

IM 01C25T02-01E

A3.4.3 STATUS_OPTS

Bit

Description

Use Uncertain as Good Causes all inputs (OP_SELECT, IN_n, and DISABLE_n) the status of which is “uncertain,” to

be handled as “good” (NC) status inputs and the others to be handled as ”bad” status inputs.

Uncertain if Man mode

When the mode is Man, the status of OUT is interpreted as “uncertain.”

(This does not apply to SELECTED.)

A3.5 List of Input Selector Block Parameters

Relative

Index

Parameter

Write

Mode

Valid Range

Initial

Value

View

Description / Remarks

1 2 3 4

0

BLOCK_

HEADER

Block

Tag=O/S

TAG: “IS”

Information relating to this function block, such as block

tag, DD revision, and execution time.

1

ST_REV

-----

-----

2 2 2 2 Indicates the revision level of the set parameters

associated with the IS block. If a setting is modified, this

revision is updated. It is used to check for parameter

changes, etc.

2

TAG_DESC

Null

A universal parameter that stores comments describing

tag information.

3

STRATEGY

1

2 A universal parameter intended for use by the high-level

system to identify function blocks.

4

ALERT_KEY

1-255

1

1 Key information used to identify the location where an

alert has occurred. Generally, this parameter is used

by the high-level system to identify specific areas in a

plant that are under the control of specific operators,

to distinguish necessary alarms only. This is one of the

universal parameters.

5

MODE_BLK

4

4

A universal parameter representing the operation status of

the IS block. It consists of the Actual, Target, Permit, and

Normal modes.

6

BLOCK_

ERR

-----

-----

2

2

Indicates the error status relating to the Input Selector

function block.
The bit used by this function block is as follows: Bit 15:

O/S mode.

7

OUT

MAN

0

5

5

Block output.

8

OUT_

RANGE

11

Set the range of OUT.

9

GRANT_

DENY

0

2

The parameter used to check if various operations

have been executed. The bits in the GRANT parameter

corresponding to various operations are set before any

of them are executed. After the operations are complete,

the DENY parameter is checked to find out if any bit

corresponding to the relevant operation has been set.

If no bit is set, it is evident that the operations have been

executed successfully.

10

STATUS_

OPTS

O/S

“Use Uncertain
as good” and
“Uncertain if
Manual” only

0

2 A user-selectable option available for status handling in

the block.

11

IN_1

0

5

5

Input 1

12

IN_2

0

5

5

Input 2

13

IN_3

0

5

5

Input 3

14

IN_4

0

5

5

Input 4

15

DISABLE_1

0, 1

0

2

2

Selector switch to disable input 1 from being selected.

16

DISABLE_2

0, 1

0

2

2

Selector switch to disable input 2 from being selected.

17

DISABLE_3

0, 1

0

2

2

Selector switch to disable input 3 from being selected.

18

DISABLE_4

0, 1

0

2

2

Selector switch to disable input 4 from being selected.

19

SELECT_

TYPE

1-6

0

1 Specifies the input selection algorithm.

Advertising