<Appendix 3. Input Selector (IS) Block>

A3-16

IM 01C25T02-01E

A3.6 Application Example

The following describes the temperature control system of a fixed bed-type reactor. In this case, there are

instances where the point showing the maximum temperature changes due to catalytic deterioration, raw

material flow, etc. Therefore, a large number of measurement points are provided, and the maximum value

obtained among these measurement points is input to the controller to control reactor temperature.

FA0310.ai

IS

PID

AI3

AI1

AI2

AI4

AO

Refrigerant

Raw material

Product

C

ata

lyti

c r

ea

cto

r

Figure A3.10 Temperature Control System of a Fixed Bed-type Reactor

IS

IN_1 4

OUT

PID

BKCAL_IN

OUT

IN

AO

CAS_IN

BKCAL_OUT

AI1

OUT

AI1

OUT

AI

OUT

AI1

OUT

AI1 AI4

FA0311.ai

Figure A3.11 Example of Scheduling

AI1: Temperature 1, AI2: Temperature 2, AI3: Temperature 3, AI4: Temperature 4

IS: SELECT_TYPE = MAX

Basic operations and work sequence:

1. The IS block obtains values and status information from AI.

2. The block selects the AI information using the alternatives.

3. The block displays and outputs the information selected by SELECTED.