Appendix 4. arithmetic (ar) block, A4.1 arithmetic function block schematic, A4.1 – Yokogawa EJX930A User Manual

Page 112: A4-1

Advertising
background image

<Appendix 4. Arithmetic (AR) Block>

A4-1

IM 01C25T02-01E

Appendix 4. Arithmetic (AR) Block

The Arithmetic (AR) block switches two main inputs of different measurement ranges seamlessly and

combines the result with three auxiliary inputs through the selected compensation function (10 types) to

calculate the output.

A4.1 Arithmetic Function Block Schematic

The diagram below shows the Arithmetic block schematic.

IN

IN_LO

IN_1

IN_2

IN_3

RANGE_LO

RANGE_HI

RANGE

EXTENSION

FUNCTION

(IN_1+BIAS_IN_1)

*

GAIN_IN_1

(IN_2+BIAS_IN_2)

*

GAIN_IN_2

(IN_3+BIAS_IN_3)

*

GAIN_IN_3

BIAS_IN_i

GAIN_IN_i

ARITH_TYPE

BAL_TIME

PV

t_1

t_2

t_3

ALGORITHM TYPE

COMP_LO_LIM

COMP_HI_LIM

func

*

GAIN

+ BIAS

OUT_HI_LIM

MAN·O/S

OUT

OUT_LO_LIM

PRE_OUT

FA0401.ai

Figure A4.1 AR Block

The Arithmetic block is divided into three sections:

• Input section: Makes a go/no-go decision on the use of an input value, switches the range, and

determines the PV status.

• Computation section: Makes calculations through ARITH_TYPE.

• Output section: Applies gain multiplication and bias addition to the calculated result to perform limitation

processing for output.

* The range extension function compensates the IN and IN_LO input values when two devices with different

ranges are connected, to make smooth input switching.

Advertising