A4.2.3 INPUT_OPTS

INPUT_OPTS has an option that handles an input

with “uncertain” or “bad” status as a “good” status

input.

Bit

Function

0

Handles IN as a “good” status input if its status

is “uncertain.”

1

Handles IN_LO as a “good” status input if its

status is “uncertain.”

2

Handles IN_1 as a “good” status input if its

status is “uncertain.”

3

Handles IN_1 as a “good” status input if its

status is “bad.”

4

Handles IN_2 as a “good” status input if its

status is “uncertain.”

5

Handles IN_2 as a “good” status input if its

status is “bad.”

6

Handles IN_3 as a “good” status input if its

status is “uncertain.”

7

Handles IN_3 as a “good” status input if its

status is “bad.”

8 to 15 Reserved

There are options called “IN Use uncertain” and

“IN_LO Use uncertain” for the IN and IN_LO inputs.

When these options are valid, IN and IN_LO are

internally interpreted as “good” IN and IN_LO even

if their statuses are “uncertain.” (There is no option

for “bad” status.)
For the IN_1, IN_2, and IN_3 auxiliary inputs, there

are options known as “IN_i Use uncertain” and “IN_i

Use bad.” If these options are valid, an IN_i with

“uncertain” or “bad” status is internally interpreted

as a “good” IN_i.
* The exception is that if the input status is “Bad.

Not Connected,” INPUT_OPTS does not apply and

the input is considered “bad” as is.

A4.2.4 Relationship between the Main

Inputs and PV

The value and PV status are determined by the

statuses of two main inputs, INPUT_OPTS, and

RANGE_LO and RANGE_HI.

• If the statuses of two main inputs are both

“good” or anything other than “good”

See A4.2.1, Main Inputs.
• If only one of two main inputs has “good” status

after application of INPUT_OPTS, the PV value

is determined as follows:

• If the status of IN is “good” and that of

“IN_LO” is anything other than “good”

IN > RANGE_LO → PV = IN

IN ≤ RANGE_LO → See A4.2.1.

• If the status of IN is anything other than

“good” and that of “IN_LO” is “good”

IN_LO < RANGE_HI → PV = IN_LO

IN_LO ≥ RANGE_H → See A4.2.1.

RANGE_LO

RANGE_HI

PV = IN_LO

PV = IN

PV = g × IN + (1-g) × IN_LO

PV = g × IN + (1-g) × IN_LO

IN

IN_LO

FA0403.ai

If the status of IN is “good” and that of “IN_LO” is

anything other than “good”

If the status of IN is anything other than “good”

and that of “IN_LO” is “good”

Advertising