A4.4.1 mode handling, A4.4.2 status handling, A4.4.1 – Yokogawa EJX930A User Manual

Page 116: A4.4.2, A4-5

Advertising
background image

<Appendix 4. Arithmetic (AR) Block>

A4-5

IM 01C25T02-01E

A4.4.1 Mode Handling

Mode

Output

Auto

OUT = PRE_OUT

MAN

For OUT, the OUT value in the Auto mode just

before change to MAN or O/S is retained.

O/S

In the Manual mode (including O/S), the value of

OUT in the Auto mode just before a change to the

Manual mode is held or the value written to OUT is

output.
If the mode is switched from Manual to Auto, the

value of OUT that is linearly changed with respect to

the value of PRE_OUT for time set by BAL_TIME is

output. The PRE_OUT always indicates the results

of calculation. After elapse of BAL_TIME, OUT =

PRE_OUT is established. Note that if the value

of BAL_TIME is changed during linear change

of the OUT value, it is not reflected. The value of

BAL_TIME will be reflected only after the mode is

changed the next time.

FA0404.ai

PRE_OUT

OUT

AUTO

MAN

AUTO

BAL_TIME

Case of BAL_TIME = 5 seconds

The value of OUT is represented by the following

equation.

yn = yn - 1 + (xn - yn - 1) / (α - n)

α = (T / tc) + 1

*: The value of T/tc truncates digits to the right of

the decimal point.

where y: OUT

x: PRE_OUT

tc: period of execution

T: BAL_TIME

n: period

A4.4.2 Status Handling

The setting of INPUT_OPTS is applied to the input

status. When INPUT_OPTS is applied, there are

cases where the PV status becomes “good” even if

the status of main inputs is “uncertain” or the status

of auxiliary inputs is “uncertain” or “bad.”
The PV status is classified by the following:

• If the statuses of two main inputs are both

“good” or anything other than “good”:

See A4.2.1, Main Inputs.
• If only one of the statuses of two main inputs is

“good”:

• If the status of IN is “good” and that of

“IN_LO” is anything other than “good”

IN > RANGE_LO

→ The status of IN applies.

IN ≤ RANGE_LO

→ See A4.2.1, Main Inputs
• If the status of IN is anything other than

“good” and that of “IN_LO” is “good”

IN_LO < RANGE_H

→ The status of IN_LO applies.

IN_LO ≥ RANGE_HI

→ See A4.2.1, Main Inputs

The exception is that if RANGE_LO > RANGE_HI,

the PV status is made “Bad. Configuration Error.”
The input status irrelevant to the computing

equation selected by ARITH_TYPE will be ignored

and does not affect other statuses. The statuses

of outputs (OUT.Status and PRE_OUT.Status) are

interpreted as the status of the worst input among

the statuses of PV and auxiliary inputs (IN_1,

IN_2, and IN_3) to which INPUT_OPTS has been

applied.
Example:

Case 1

Case 2

Case 3

PV

Good

IN_1

Unceriain

IN_2

Bad

IN_3

Bad

INPUT_

OPTS

IN_1 Handled as a

“good” input

if its status is

“uncertain.”

No option

IN_2 Handled as a “good” input

if its status is “bad.”

No option

IN_3

No option

ARITH_TYPE 1) Flow compensation (linear) in

A4.3.1, “Computing Equations”

OUT.Status

Good

Uncertain

Bad