<Appendix 5. PID Block>

A5-4

IM 01C25T02-01E

A5.4 PID Computation Details

A5.4.1 PV-proportional and -derivative

Type PID (I-PD) Control Algorithm

For PID control, the PID block employs the PV-

proportional and PV-derivative type PID control

algorithm (referred to as the I-PD control algorithm)

in Auto and RCas mode. The I-PD control algorithm

ensures control stability against sudden changes in

the setpoint, such as when the user enters a new

setpoint value. At the same time, the I-PD algorithm

ensures excellent controllability by performing

proportional, integral, and derivative control

actions in response to changes of characteristics

in the controlled process, changes in load, and

occurrences of disturbances.
In Cas mode, PV derivative type PID control

algorithm (referred to as the PI-D control algorithm)

is employed in order to obtain better performance

against the changes in the setpoint. The algorithm

is automatically switched by the block according

to the mode. A basic form of each algorithm is

expressed in the equation below.

∆MVn = K{∆PVn + (PVn - SPn) + ∆(∆PVn)}

∆T

Ti

Td

∆T

I-PD Control Algorithm (in Auto / RCas mode)

∆MVn = K{∆(PVn - SPn) + (PVn - SPn)

∆T

Ti

Td

∆T

PI-D Control Algorithm (in Cas mode)

+ ∆(∆PVn)}

Where,

ΔMVn = change in control output

ΔPVn = change in measured (controlled)

value = PVn - PVn-1

ΔT

= control period = period_of_execution

in Block Header

K

= proportional gain = GAIN (= 100/

proportional band)

Ti

= integral time = RESET

Td

= derivative time = RATE

The subscripts, n and n-1, represent the time

of sampling such that PVn and PVn-1 denote

the PV value sampled most recently and the PV

value sampled at the preceding control period,

respectively.

A5.4.2 PID Control Parameters

The table below shows the PID control parameters.

Parameter

Description

Valid Range

GAIN

Proportional gain 0.05 to 20

RESET

Integral time

0.1 to 10,000 (seconds)

RATE

Derivative time

0 to infinity (seconds)

A5.5 Control Output

The final control output value, OUT, is computed

based on the change in control output ΔMVn, which

is calculated at each control period in accordance

with the aforementioned algorithm. The PID block

in an EJX performs the velocity type output action

for the control output.

A5.5.1 Velocity Type Output Action

The PID block determines the value of the new

control output OUT by adding the change in control

output calculated in the current control period,

ΔMVn, to the current read-back value of the MV,

MV

RB

(BKCAL_IN).

This action can be expressed as:
ΔMVn’ = ΔMVn

*

(OUT_SCALE. EU100 – OUT_

SCALE. EU_0) / (PV_SCALE. EU_100 – PV_

SCALE. EU_0)

(Direct Acting is False in CONTROL_OPTS)

OUT = BKCAL_IN – ΔMVn’

(Direct Acting is True in CONTROL_OPTS)

OUT = BKCAL_IN + ΔMVn’

A5.6 Direction of Control Action

The direction of the control action is determined by

the Direct Acting setting in CONTROL_OPTS.

Value of Direct

Acting

Resulting Action

True

The output increases when the input

PV is greater than the setpoint SP.

False

The output decreases when the input

PV is greater than the setpoint SP.