<Appendix 5. PID Block>

A5-6

IM 01C25T02-01E

Transition

Destination

Mode

Condition

NOT

Conditions

RCas* **

7. If RCas is set in

MODE_

BLK.target

- AND -

if neither

IN.status (input

status) nor

RCAS_

IN.status is Bad.

NOT if any

one or more

of conditions 1

to 3 are met.

ROut* **

8. If ROut is set in

MODE_

BLK.target

- AND -

if

ROUT_IN.status (input

status) is not Bad.

NOT if any

one or more

of conditions 1

to 3 are met.

In accordance

with the

SHED_OPT

setting

9. If

RCAS_IN.status or

ROUT_IN.status is Bad

(indicating a computer

failure; see Section A5.17.1

for details).

*

To activate mode transitions to Auto, Cas, RCas,

and ROut, the respective target modes must be set

beforehand to MODE_BLK.permitted.

**

A transition to Cas, RCas, or ROut requires that

initialization of the cascade connection has been

completed.

A5.10 Bumpless Transfer

Prevents a sudden change in the control output

OUT at changes in block mode (MODE_BLK) and

at switching of the connection from the control

output OUT to the cascaded secondary function

block. The action to perform a bumpless transfer

differs depending on the MODE_BLK values.

A5.11 Setpoint Limiters

Active setpoint limiters that limit the changes in the

SP value, differ depending on the block mode as

follows.

A5.11.1 When PID Block Is in Auto Mode

When the value of MODE_BLK is Auto, the four

types of limiters are in force: high limit, low limit,

rate-of-increase limit, and rate-of-decrease limit.

Setpoint High/Low Limits

• A value larger than the value of SP_HI_LIM

cannot be set for SP.

• A value smaller than the value of SP_LO_LIM

cannot be set for SP.

Setpoint Rate Limits
The setpoint rate limits are used to restrict the

magnitude of changes in the SP value so as to

change the SP value gradually towards a new

setpoint.

• An increase of the SP value at each execution

period (period of execution in the Block Header)

is limited to the value of SP_RATE_UP.

• A decrease of the SP value at each execution

period (period of execution in the Block Header)

is limited to the value of SP_RATE_DOWN.

A5.11.2 When PID Block Is in Cas or RCas

Mode

By selecting Obey SP Limits if Cas or RCas in

CONTROL_OPTS (see Section A5.13), the setpoint

high/low limits can be put into force also when the

value of MODE_BLK is Cas or RCas.