A7.4 software download sequence, A7.5 download files, A7.4 – Yokogawa EJX930A User Manual

Page 139: A7.5, A7-2, Caution

Advertising
background image

<Appendix 7. Software Download>

A7-2

IM 01C25T02-01E

A7.4 Software Download

Sequence

The flowchart below outlines the software download

procedure. Although the time taken for the entire

procedure varies depending on the size of the field

bus device’s software, it generally take about 20

minutes where there is a one-to-one connection

between a fieldbus device and download tool, and

longer when multiple field devices are connected to

the fieldbus.

FA0702.ai

Start download tool

Select file(s)

Select device(s)

Carry out download

Activate device(s)

Select the software file(s) you

want to download.

Select the device(s) to which you

want to download software.

Transmit the software to the field

device(s).

Activate the device(s) to start with

new software.

Figure A7.2 Flow of Software Download Procedure

CAUTION

Carrying out a software download leaves the

PD tag, node address, and transducer block

calibration parameters that are retained in the

nonvolatile memory inside the target device,

but may reset other parameters to the defaults

(except a minor update that does not change

the number of parameters). Hence, where

necessary, save the parameters using an

engineering tool, parameter setting utility, or the

like before carrying out a software download,

and then reconfigure the field device(s) after the

download. For details, see Section A7.6.

CAUTION

The current dissipation of the target field

device increases transitorily immediately after

a download due to erasing of the FlashROM’s

contents. Use a fieldbus power supply which

has sufficient capacity to cover such increases in

feed current.

CAUTION

Upon completion of the activation, the target

fieldbus device performs resetting internally,

which temporarily halts fieldbus communication

and function block executions. Be especially

careful about a valve positioner; the output air

pressure will fall to the minimum level (i.e., zero).

CAUTION

Do not turn off the power to a field device or

disconnect the download tool during a download

or activation. The device may fail as a result.

NOTE

Be careful about the noise on the fieldbus link. If

the fieldbus is noisy, the downloading may take a

very long time or fail.

A7.5 Download Files

Download files have the following filenames (with

the filename extension of “.ffd”). Take care to

choose the correct download file for the target field

device:

“594543” + device family + “_” + device type +

“_” + domain name + “_” + software name + “_”

+ software revision + “.ffd”

For example, the name of the download file for an

EJX may have the following name:

594543000C_000C_EJX_ORIGINAL_R101.ffd

Refer to A7.11(3) DOMAIN_HEADER about each

keyword of the file name.
The device type is “000C” for an EJX transmitter,

and is "0011" for an EJA transmitter.
The software name is “ORIGINAL” or “UPDATE.”

The former indicates an original file and the latter

an update file. Whenever performing a download

to update the device revision, obtain the original file.

In general, an addition to the parameters or blocks

requires a device revision update.

Advertising