<Appendix 8. Advanced Diagnostics>

A8-3

IM 01C25T02-01E

A8.2.1 Blockage Detection

DIAG_LIM

When the parameter based on pressure fluctuation

exceeds the preset value, EJX diagnoses an

impulse line as blockage and gives an alarm. The

threshold values are set to DIAG_LIM [1] to [8] in

the SENSOR Transducer block.
TableA8.2 shows the default values at the factory

setting, which are different according to the model.

NOTE

• When ILBD is performed for the first time,

use the default value. If the pressure

fluctuation amplitude is low or a false alarm

is often generated after ILBD is performed,

change the values of DIAG_LIM according to

the procedure described in A8.2.10.

• Use Device description (DD) file for

parameter setting.

DIAG_LIM

#

Parameter

Threshold value

[1] fdpmax

Threshold to detect “A Blocking” by

using

RATIO_FDP

[2] fdpmin

Threshold to detect “B Blocking” by

using

RATIO_FDP

[3] fsplmax

Threshold to detect “Large

Fluctuation of Low Side” by using

RATIO_FSPL

[4] fsplmin

Threshold to detect “Low Side

Blocking” by using

RATIO_FSPL

[5] fsphmax

Threshold to detect “Large

Fluctuation of High Side” by using

RATIO_FSPH

[6] fsphmin

Threshold to detect “High Side

Blocking” by using

RATIO_FSPH

[7] blkfmax

Threshold to detect “High Side

Blocking” by using

VALUE_BLKF

[8] blkfmin

Threshold to detect “Low Side

Blocking” by using

VALUE_BLKF

[9] dpavgmax

Threshold to detect “Outside

Diagosis Range” by using

VALUE_

DPAVG and to detect “Invalid

Ref xx” by using

REFERENCE_

DPAVG.

[10] dpavgmin

Threshold to detect “Outside

Diagosis Range” by using

VALUE_

DPAVG and to detect “Invalid

Ref xx” by using

REFERENCE_

DPAVG.

Table A8.2 Default Values of DIAG_LIM

INDEX

Parameter

Differential pressure

transmitter

Flange

mounted

differential

pressure

transmitter

Diaphragm

sealed

differential

pressure/

pressure

transmitter

Absolute

pressure

transmitter

Gauge

pressure

transmitter

Gauge/

Absolute

pressure

transmitter

EJX110A

EJX115A

EJX120A EJX130A

EJX135A

EJX210A

EJX118A

Note 1

EJX438A

EJX310A

EJX430A
EJX440A

EJX510A

EJX530A

[1]

fDPmax

3

3

3

10000

10000

10000

10000

10000

[2]

fDPmin

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

[3]

fSPlmax

5

10000

5

10000

10000

10000

10000

10000

[4]

fSPlmin

0.5

0

0.5

0

0

0

0

0

[5]

fSPhmax

5

10000

5

10000

10000

10000

10000

10000

[6]

fSPhmin

0.5

0

0.5

0

0

0

0

0

[7]

blkfmax

0.6

10

0.6

10

10

10

10

10

[8]

blkfmin

-0.6

-10

-0.6

-10

-10

-10

-10

-10

[9]

dpavgmax

Note2

1

1

1

1

1

1

1

1

[10]

dpavgmin

Note2

0.05

0.2

0.05

-1

-1

0.05

0.05

0.05

Note 1: The default values are set for level measurement. If EJX118A is applied to the flow measurement, set the same value to

DIAG_LIM [1] to [10] as those of EJX110A.

Note 2: It indicates the threshold value for ILBD over range (refer to A8.2.5.3).