<Appendix 8. Advanced Diagnostics>

A8-5

IM 01C25T02-01E

Large Fluctuation Detection

When a pump or compressor starts, the large

fluctuation is generated as process condition

changes rapidly. This phenomenon affects process

fluctuation measurement, so correct blockage

detection is not performed.
If “Large fluctuation of Low Side” or “Large

fluctuation of High Side” is detected, consider

whether a blockage result is correct.
The threshold values to detect large fluctuation are

set to DIAG_LIM [3] and [5].
Since these values are enough to detect large

fluctuation, it is not almost necessary to change

them.

A8.2.2 Combination of Reference Result

and Blockage Detection

An EJX differential pressure transmitter can detect

four modes of impulse line blockage: both-sides,

high-pressure side, low-pressure side, and/or

single-side when all the reference values are

properly measured. However, the detectable alarm

mode combination is limited when some of the

reference values are invalid. The relation between

the detectable blockage modes and reference value

results are shown in the below figure.

NOTE

• REFERENCE_FDP must be larger than the

specified level shown in Table A8.3 (refer

A8.2.6). No blockage can be detected when

VALUE_FDP is not large enough.

• The plausibility of blockage detection needs

to be confirmed by blockage simulation test.

The simulation test can be performed by

the appropriate manifold operation (refer to

A8.2.8).

[Differential pressure transmitter]

Fluctuation Parameters

Simulation Test

Available Blockage Detection

REFERENCE_FDP

OK

REFERENCE_FSPL

OK

REFERENCE_FSPH

OK

REFERENCE_BLKF

OK

• Test for low-pressure side

• Test for high-pressure side

• Test for both-pressure sides

• B Blocking detection

(by using RATIO_FDP)

• Low side blockage detection

(by using RATIO_FSPL)

• High side blockage detection

(by using RATIO_FSPH)

• High/Low side blockage detection

(by using VALUE_BLKF )

REFERENCE_FDP

OK

REFERENCE_FSPL

OK

REFERENCE_FSPH

OK

REFERENCE_BLKF

NG

• Test for low-pressure side

• Test for high-pressure side

• Test for both-pressure sides

• A/B Blocking detection

(by using RATIO_FDP)

• Low Side Blocking detection

(by using RATIO_FSPL)

• High Side Blocking detection

(by using RATIO_FSPH)

REFERENCE_FDP

OK

REFERENCE_FSPL

NG

REFERENCE_FSPH

OK

REFERENCE_BLKF

NG

• Test for high-pressure side

• A Blocking detection

(by using RATIO_FDP)

• High Side Blocking detection

(by using RATIO_FSPH)

REFERENCE_FDP

OK

REFERENCE_FSPL

NG

REFERENCE_FSPH

NG

REFERENCE_BLKF

NG

• Test for both-pressure sides

• B Blocking detection

(by using RATIO_FDP)

[Transmitter for gauge/absolute pressure and level measurement]

Fluctuation Parameters

Simulation Test

Available Blockage Detection

REFERENCE_FDP

OK

• Test for high-pressure side

• B Blocking detection

(by using RATIO_FDP)