<Appendix 8. Advanced Diagnostics>

A8-6

IM 01C25T02-01E

A8.2.3 Operating Parameters

DIAG_MODE

DIAG_MODE gives the directive for the ILBD

operation. There are following three modes.

DIAG MODE

Code

Mode

Function

0

Stop

The blockage detection operation

is stopped.

1

Calculation The blockage detection operation

is performed.

Alarms are generated along with

the result.

2

Reference Reference values for the

blockage detection are obtained

and updated to the latest. After

sampling reference values, this

mode changes to "Calculation".

When the blockage detection operation is

performed, set “Calculation” to DIAG_MODE.

“Stop” must be set when you change a threshold

value or set an alarm.

“Reference” is set in order to obtain the reference

fluctuation values under the normal configuration.

DIAG_PERIOD

The values such as RATIO_FDP and BLKF are

averaged based on several hundreds of pressure

fluctuation values in constant time. DIAG_PERIOD

defines the sampling time. The default value at the

shipment is set to 180 seconds.
For the information on how to change the sampling

period, refer to A8.2.10.

DIAG_COUNT

When the value as RATIO_FDP or BLKF exceeds

the threshold value for several times in a row, it is

estimated that the impulse line is plugged. DIAG_

COUNT defines the number of times to estimate

blockage detection.
If DIAG_COUNT is set to three times, an alarm is

not generated at part ‘A’ in Figure A8.3. The reason

is that only the first and second values exceeded

consecutively the threshold.
When the value exceeds consecutively the

threshold value three times, an alarm is generated

(see part ‘B’ in Figure A8.3).

B

A

B

A

FA0804.ai

DIAG_COUNT(Number of times: 3)

DIAG_COUNT(Number of times: 3)

DIAG_PERIOD

DIAG_PERIOD

Upper Threshold(DIAG_LIM)

Lower Threshold(DIAG_LIM)

An alarm is generated.

An alarm is generated.

Time

Time

Figure A8.3 Relationship of DIAG_COUNT and

Alarm

The number of detection to give an alarm is set for

each blockage detection function. The default value

at the shipment is set to three times.
If fluctuating around the threshold value, an alarm

may be often generated. In this case, change the

threshold value (DIAG_LIM) or the sampling time

(DIAG_PERIOD) to enhance the accuracy of the

blockage detection. Refer to A8.2.10.