A8.2.6 condition check, A8.2.7 obtain reference values, A8.2.6 – Yokogawa EJX930A User Manual

Page 154: A8.2.7, A8-10

Advertising
background image

<Appendix 8. Advanced Diagnostics>

A8-10

IM 01C25T02-01E

A8.2.5.5 Reflect Blockage to PV/SV/TV

Status

“Reflect Blockage to PV/SV/TV Status”

corresponding to bit 15 in DIAG_OPTION is

used to link the alarm to the OUT signal status of

PRIMARY_VALUE, SECONDARY_VALUE, and

TERTIARY_VALUE.
When the ILBD algorithm detects the abnormality,

each signal status becomes “UNCERTAIN: Non

Specific”.
The alarm is linked to the signal status of PV, SV

and TV, according to the following procedure.

1) Set "Stop" to DIAG_MODE.

2) Check the checkbox of “Availability for the

Status” of DIAG_OPTION.

Note:Set to “Calculation” after setting the parameters.

NOTE

The alarms of "Invalid Ref xx", "Outside

Diagnosis Range" do not link to the signal status

of PV, SV, and TV.

A8.2.6 Condition Check

After the EJX differential pressure/pressure

transmitter was installed, it is necessary to confirm

that the Primary Value (PV) is stable under the

normal operating condition and that fluctuation

amplitude under the normal operating condition is

large enough to detect the blockage.

A8.2.6.1 Stability of Primary Value

1) Observe the value change of PRIMARY_

VALUE under the normal operating condition

for 10 minutes.

2) Confirm the value change is less than 10%.

If the value change is more than 10%, the error

influences pressure fluctuation value so that the

blockage detection becomes Unreliable. You need

to consider the plant operating conditions.

A8.2.6.2 Fluctuation Value

NOTE

The blockage detection may not be carried

out correctly when pressure fluctuation

amplitude especially with the pressure and level

measurement, is small.

Confirm that each value of VALUE_FDP, VALUE_

FSPL, VALUE_FSPH, and VALUE_BLKF is more

than the value specified in the below table.

Table A8.3 Requiremnents to apply ILBD

Condition

VALUE_FDP

7×10

-10

or more

VALUE_FSPL

1×10

-10

or more

VALUE_FSPH

1×10

-10

or more

VALUE_BLKF

-0.5 to 0.5

VALUE_FDP is not enough

No blockage can be detected if VALUE_FDP is not

larger than the specified value.

Only VALUE_FDP is enough

“A Blocking” or “B Blocking” can be detected if

VALUE_FSPL and VALUE_FSPH are not larger

than specified values.

VALUE_FDP and VALUE_FSPL are enough

“High Side Blocking” and “Large Fluctuation of High

Side” can not be detected if VALUE_FSPH is not

larger than specified value.

VALUE_FDP and VALUE_FSPH are enough

“Low Side Blocking” and “Large Fluctuation of Low

Side” can not be detected if VALUE_FSPL is not

larger than specified value.

VALUE_FDP, VALUE_FSPL and VALUE_FSPH

are enough

All alarm modes can be detected even if VALUE_

BLKF is not within the specified values.

A8.2.7 Obtain Reference Values

The pressure fluctuation values are reduced

when the impulse line is plugged. Therefore, the

reference value is required to determine the degree

of reduction

Advertising