<Appendix 8. Advanced Diagnostics>

A8-11

IM 01C25T02-01E

IMPORTANT

• If the impulse line is about to be plugged at

the time when a reference value is obtained,

blockages cannot be detected accurately.

The impulse lines on both the high-pressure

and low-pressure sides need to be cleaned

before a reference value is obtained.

• All air bubbles need to be adequately purged

before a reference value is obtained.

• Reference values must be obtained under

operating condition.

• Do not obtain the reference values when the

BLOCK_MODE of SENSOR Transducer is

OOS. If carried out, an alarm of "Invalid Ref

xx" is generated.

Start of Sampling

The sampling of reference value is carried out

for 180 seconds, which is the default value set to

DIAG_PERIOD.

1) Confirm that the sampling period

(DIAG_PERIOD) is set to 180 seconds.

2) Set “Reference” to DIAG_MODE.

The sampling starts soon after the setting.

IMPORTANT

• For the each parameter, the one value is

given. If “Reference” is set to DIAG_MODE

again, the value is updated and overwritten.

• If the power supply is shut down during the

sampling, DIAG_MODE becomes “Stop”.

Set “Reference” to DIAG_MODE in order to

carry out the sampling again.

End of Sampling

After about 180 seconds, the sampling

automatically finishes. The “Reference” setting

of DIAG_MODE changes automatically to

“Calculation” and the termination time is recorded to

REFERENCE_TIME.

1) Confirm that the setting of DIAG_MODE

changes to “Calculation”.

2) Check the termination time recorded into

REFERENCE_TIME.

Reference Values

Confirm the latest values are obtained into the

following parameters.

• REFERENCE_FDP

• REFERENCE_FSPL

• REFERENCE_FSPH

• REFERENCE_BLKF

• REFERENCE_DPAVG

Invalid Ref BlkF, fSPh, fSPl, or fDP

When the enough reference fluctuation value is not

obtained, an alarm of Invalid Reference value for

each parameter is generated and also the part of

ILBD function related to the Invalid Ref BlkF, fSPh,

fSPl, or fDP is not carried out.
Confirm the alarm of Invalid Ref BlkF, fSPh, fSPl, or

fDP is not displayed in DIAG_ERR.
If an alarm of Invalid Reference value is generated,

consider the process condition or obtain the

reference fluctuation values again.

NOTE

Even if an alarm of Invalid Ref BlkF, fSPh, fSPl,

or fDP is generated, “Calculation” in DIAG_

MODE is kept.

A8.2.8 Capability Test of Blockage

Detection Operation

Before performing the ILBD operation, check the

capability of the blockage detection operation.

The simulation test is performed by closing motion

of a three-valve manifold or stop valve. When

simulated blockage occurs, confirm that an alarm is

generated.

NOTE

The fluctuation amplitude of atmospheric

pressure is nearly zero with pressure or level

measurement. In such case, simulate the

blockage detection by closing the valve where

the fluctuation existed.

Simulation of High-pressure-side

Blockage

1) Close the high-pressure-side valve.

2) Confirm the value of PRIMARY_VALUE is

stable. If unstable, open valve a little.