<Appendix 8. Advanced Diagnostics>

A8-12

IM 01C25T02-01E

3) Set “Calculation” to DIAG_MODE so as to start

blockage detection operation.

4) Check that an alarm of “High Side Blocking” is

generated after the time that consists of DIAG_

PERIOD and DIAG_COUNT passed.

5) Check also the operation of the analog alert if

an analog alert is set.

6) Open the valve completely and check that there

are no alarms.

Simulation of Low-pressure-side

Blockage

1) Close the low-pressure-side valve.

2) Confirm the value of PRIMARY_VALUE is

stable. If unstable, open valve a little.

3) Set “Calculation” to DIAG_MODE so as to start

blockage detection operation.

4) Check that an alarm of “Low Side Blocking” is

generated after the time that consists of DIAG_

PERIOD and DIAG_COUNT passed.

5) Check also the operation of the analog alert if

an analog alert is set.

6) Open the valve completely and check that there

are no alarms.

Simulation of Both-pressure-side

Blockage

1) Close the both-pressure-side valves.

2) Confirm the value of PRIMARY_VALUE is

stable. If unstable, open valve a little.

3) Set “Calculation” to DIAG_MODE so as to start

blockage detection operation.

4) Check that an alarm of “B Blocking” is

generated after the time that consists of DIAG_

PERIOD and DIAG_COUNT passed.

5) Check also the operation of the analog alert if

an analog alert is set.

6) Open the valves completely and check that

there are no alarms.

A8.2.9 Start ILBD Operation

If process condition and capability to detect a

blockage are confirmed, the ILBD operation can be

started according to the following procedure.

1) Check the value of sampling period

(DIAG_PERIOD).

2) Check the number of times that detect the

blockage consecutively in order to give an

alarm (DIAG_COUNT). The default value at the

shipment is set to 3 times.

3) Set “Calculation” status to DIAG_MODE.

If the reference value has not yet been

obtained, set “Reference” to DIAG_MODE.

After obtained the reference values, the ILBD

starts automatically. At the same time, DIAG_

MODE changes automatically from “Reference”

to “Calculation”.

A8.2.10 Tuning

When the pressure fluctuation amplitude in fluids is

not sufficiently large or an alarm is often generated

according to the process condition, tune up by

changing the threshold for the blockage detection

(DIAG_LIM) or the sampling period (DIAG_

PERIOD) to enhance the accuracy of the blockage

detection.
The ILBD operation must be stopped to tune up.

Set “Stop” to DIAG_MODE.

A8.2.10.1 Threshold Value

The figure below shows the image of tuning effect

with a monochrome bar.

FA0809.ai

0

1

3

Threshold (lower side)

Threshold (upper side)

1) DIAG_LIM [2]

2) DIAG_LIM [4]

3) DIAG_LIM [6]

1) DIAG_LIM [1]

2) DIAG_LIM [3]

3) DIAG_LIM [5]

(a) The tuning image of the threshold values for

1) RATIO_FDP Sqrt

(VALUE_FDP/REFERENCE_FDP),

2) RATIO_FSPL Sqrt

(VALUE_FSPL/REFERENCE_FSPL),

3) RATIO_FSPH Sqrt

(VALUE_FSPH/REFERENCE_FSPH)

(b) The tuning image of the threshold values for

4) Sqrt (VALUE_BLKF/REFERENCE_BLKF)

0

-1

1

Threshold (lower side)

Threshold (upper side)

4) DIAG_LIM [8]

4) DIAG_LIM [7]

Figure A8.7 Tuning Image of Threshold Value