<2. Handling Cautions>

2-5

IM 01C25T02-01E

FNICO Rules

The FNICO Concept allows the interconnection of

nonincendive field wiring apparatus to associated

nonincendive field wiring apparatus not specifically

examined in such combination. The criterion for

such interconnection is that the voltage (Vmax),

the current (Imax) and the power (Pmax) which

nonincendive field wiring apparatus can receive and

remain nonincendive, considering faults, must be

equal or greater than the voltage (Uo, Voc or Vt),

the current (Io, Isc or It) and the power (Po) which

can be provided by the associated nonincendive

field wiring apparatus (supply unit). In addition the

maximum unprotected residual capacitance (Ci)

and inductance (Li) of each apparatus (other than

terminators) connected to the Fieldbus must be less

than or equal to 5nF and 10uH respectively.
In each N.I. Fieldbus segment only one active

source, normally the associated nonincendive

field wiring apparatus, is allowed to provide the

necessary power for the Fieldbus system. The

allowed voltage (Uo, Voc or Vt) of the associated

nonincendive field wiring apparatus used to supply

the bus cable must be limited to the range 14Vdc

to 17.5Vdc. All other equipment connected to the

bus cable has to be passive, meaning that the

apparatus is not allowed to provide energy to the

system, except a leakage current of 50É A for each

connected device. Separately powered equipment

needs galvanic isolation to ensure the nonincendive

field wiring Fieldbus circuit remains passive.

Cable
The cable used to interconnect the devices needs

to comply with the following parameters:

Loop resistance R': 15...150 Ω/km

Inductance per unit length L': 0.4...1 mH/km

Capacitance per unit length C': 80....200 nF/km

C' =C' line/line+0.5 C' line/screen, if both lines

are floating or C' = C' line/line + C'line/screen, if

thescreen is connected to one line.

Length of spur cable: max. 30 m

Length of trunk cable: max. 1 km

Length of splice: max = 1 m

Terminators
At the end of each trunk cable an FM Approved line

terminator with the following parameters is suitable:

R= 90...100 Ω

C = 0 ....2.2 uF

2.1.2 CSA Certification

a. CSA Explosionproof Type
Caution for CSA explosionproof type.
Note 1. The transmitters with optional code /CF1

are applicable for use in hazardous

locations:

Certificate: 2014354

• Applicable Standard:

C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5,

C22.2 No.25, C22.2 No.30, 22.2 No.94,

C22.2 No.61010-1-04, C22.2 No.60079-0,

C22.2 No.60079-1

• Explosion-proof for Class I, Groups B, C and

D.

• Dustignition-proof for Class II/III, Groups E, F

and G.

• Enclosure: NEMA 4X, IP66/IP67

• Temperature Code: T6...T4

• Ex d IIC T6...T4

• Enclosure: IP66 and IP67

• Maximum Process Temperature:

120°C (T4), 100°C (T5), 85°C (T6)

• Ambient Temperature:

–50* to 75°C (T4), –50* to 80°C (T5),

–50* to 75°C (T6)

* –15°C when /HE is specified.

• Supply Voltage: 32 V dc max.

• Output Signal: 15 mA dc

Note 2. Wiring

• All wiring shall comply with Canadian

Electrical Code Part I and Local Electrical

Codes.

• In hazardous location, wiring shall be in

conduit as shown in the figure.

• WARNING:

A SEAL SHALL BE INSTALLED WITHIN

50cm OF THE ENCLOSURE.

UN SCELLEMENT DOIT ÊTRE INSTALLÉ À

MOINS DE 50cm DU BOÎTIER.

• WARNING:

WHEN INSTALLED IN CL.I, DIV 2, SEAL

NOT REQUIRED.

UNE FOIS INSTALLÉ DANS CL I, DIV 2,

AUCUN JOINT N'EST REQUIS.

Note 3. Operation

• WARNING:

AFTER DE-ENERGIZING, DELAY 5

MINUTES BEFORE OPENING.

APRÉS POWER-OFF, ATTENDRE 5

MINUTES AVANT D'OUVRIR.