<Appendix 8. Advanced Diagnostics>

A8-17

IM 01C25T02-01E

A8.2.13 Checklist

Fill out the below checklist according to the operation flow of the ILBD in order to keep the important

information for the blockage detection.

Checklist (1/5)

No.

Items

Parameters

Result

Example

1 Enable Analog Alert to Be Generated

• Uncheck the checkbox of “Diag Alm

Disable” in ALARM_SUM.

ALARM_SUM (Index: 2063)

“Diag Alm Disable”

2 Priority Setting of Analog Alert

• Enter a value of more than 3 to DIAG_

PRI. (3 is recommended.)

DIAG_PRI (Index: 2068)

3

3 Stability of PRIMARY_VALUE

(differential pressure/pressure) under

normal condition

• Check that the status of PRIMARY_

VALUE is “GOOD”.

• Check the maximum and minimum

values of PRIMARY_VALUE.

Status

Good

PRIMARY_VALUE (Index: 2014)

Max.:

Min.:

Max.: 12.3 kPa

Min.: 12.1 kPa

4 VALUE_FDP under normal condition

• Check that the value of VALUE_FDP is

more than 7×10

-10

.

VALUE_FDP (Index: 2086)

5 Start to obtain Reference values

• Set Reference to DIAG_MODE.

DIAG_MODE (Index: 2066)

6 End of Reference Value Sampling

• Check that DIAG_MODE is

“Calcuration”, after the time set to

DIAG_PERIOD passed.

DIAG_MODE (Index: 2066)

7 Alarm setting

• Record the status of Checkbox in

DIAG_OPTION.

DIAG_OPTION (Index: 2072)

A Blocking

Large Fluctuation of Low Side

Large Fluctuation of High Side

Low Side Blocking

High Side Blocking

B Blocking

Invalid Ref BlkF

Invalid Ref fSPh

Invalid Ref fSPl

Invalid Ref fDP

Outside Diagnosis Range

Reflect Blockage to PV/SV/TV

Status