<Appendix 8. Advanced Diagnostics>

A8-22

IM 01C25T02-01E

A8.3 Heat Trace Monitoring

The EJX with Heat trace monitoring function

calculates the flange temperature by using the two

temperature sensors built in the EJX. An analog

alert is generated if the temperature reached to the

preset level.
The flange temperature is based on the following

parameters and calculation formula.

[Parameters]

Parameter name

Explanation

CAP_TEMP_VAL (CT)

Measured capsule

temperature value

AMP_TEMP_VAL (AT)

Measured amplifier

temperature value

FLG_TEMP_VAL (FT)

Flange temperature value

(Calculated value)

FLG_TEMP_COEF (Cf) Coefficient to calculate flange

temperature

FLG_TEMP_H_LIM

Threshold to generate Flg

Temp High Alarm

FLG_TEMP_L_LIM

Threshold to generate Flg

Temp Low Alarm

Amplifier

Temperature
Capsule

Temperature

SENSOR Transducer Block

PRIMARY_VALUE

AMP_TEMP_VAL

CAP_TEMP_VAL

Calculation of

FLANG_TEMP_VAL

FLG_TEMP_COEFF

CT + (CT - AT) x Cf

Heat Trace Monitoring

FLG_TEMP_H_LIM

FLG_TEMP_L_LIM

FLG_TEMP_VAL

DIAG_ERR

DIAG_OPTION

ALM_SUM.disadle

DIAG_PRI

FLG_TEMP_ALM

Alarm and Alert

AI function

Block

CHANNEL=1

CHANNEL=5

CHANNEL=4

HI_LIM

LO_LIM

Resorce

Block

DEVICE_

STATUS[7]

LCD

FA0810.ai

CHANNEL=6

Figure A8.8 Functional Block Diagram of Heat Trace Monitoring

[Calculation formula]

FLG_TEMP_VAL(FT) = CT + C

f

× (CT - AT)

The FLG_TEMP_VAL (FT) is assigned to Process

Value (PV) in the AI function block. If the flange

temperature exceeds the value preset to the

HI_LIM, LO_LIM, HI_HI_LIM, or LO_LO_LIM in the

AI function block, an analog alert is generated.

NOTE

The flange temperature is calculated by the

calculation formula assumed that the capsule

part of EJX is heated up or kept warm by an

electrical heater or steam. In the case of an

atmosphere temperature or less, the difference

of temperature of approximately 3 to 4°C

may occur because the amplifier temperature

becomes higher than the capsule temperature.