A8.3.1 flg_temp_coef setting, A8.3.2 alert and alarm setting, A8.3.4 analog alert – Yokogawa EJX930A User Manual

Page 167: A8.3.5 out of temperature measurement range, A8.3.1, A8.3.2, A8.3.3, A8.3.4, A8.3.5, A8-23

Advertising
background image

<Appendix 8. Advanced Diagnostics>

A8-23

IM 01C25T02-01E

A8.3.1 FLG_TEMP_COEF Setting

The value calculated according to the following

procedure is set to the FLG_TEMP_COEFF.

• To enhance the calculation accuracy of the

flange temperature, measure the actual flange

temperature by using the temperature sensor

etc.

• Calculate the ratio of the capsule temperature

to the capsule temperature minus the amplifier

temperature from the two temperature values

measured by EJX.

• Derive the FLG_TEMP_COEF from the

measured flange temperature and the ratio

of the capsule temperature to the amplifier

temperature in accordance with the following

calculation formula.

FLG_TEMP_COEFF(C

f

) =

(Actual measured value of Flange temperature) - CT

CT - AT

A8.3.2 Alert and Alarm Setting

The abnormal results of flange temperature (heat

trace monitoring) are given by an alert or the LCD

display of alarm status.
The flange temperature changes when the heat

trace breaks or the abnormal temperature is

detected due to the failure.
The abnormal results are stored in the bit 13 and

14 of DIAG_ERR in the SENSOR Transducer

Block when the flange temperature is out of the

range between the limits preset to the following

parameters.

• FLG_TEMP_H_LIM

• FLG_TEMP_L_LIM

Generating an alarm or alert is set by DIAG_

OPTION.

Refer to A8.2.5 for the detail.

A8.3.3 Assignment of FLG_TEMP_VAL to

Process Value (PV) in AI Function

block

The EJX has four AI function blocks which of

each has one channel. If set 6 to the channel of AI

function block, the FLG_TEMP_VAL is assigned to

Process Value (PV) in AI function block. The unit of

the flange temperature follows the setting of XD_

SCALE in the assigned AI function block.
To Assign CAP_TEMP_VAL or AMP_TEMP_VAL to

Process Value (PV) in AI function block, set 4 or 5 to

the channel of AI function block.

A8.3.4 Analog Alert

Since Flange temperature is assigned to an AI

Function Block, an analog alert can be generated

by OUT_D in AI Block.
For the detail of the analog alert setting, refer to

6.6.5.

A8.3.5 Out of Temperature Measurement

Range

If the measurement value of the capsule

temperature or the amplifier temperature is out of

the measurement range, the OUT signal status

of PRIMARY_VALUE, SECONDARY_VALUE,

and TERTIARY_VALUE becomes “Uncertain-

Subnormal" and the status of CAP_TEMP_VAL,

AMP_TEMP_VAL, and FLG_TEMP_VAL become

“Uncertain-Sensor Conversion not Accurate”.
The measurement range of the capsule

temperature and the amplifier temperature is as

follows.

• Amplifier temperature: -40 to 85°C

• Capsule temperature: -40 to 120°C

The out of range is detected by the margin of 10°C

added with the measurement range.