A8.3.6 status error, A8.3.6, A8.3.7 – Yokogawa EJX930A User Manual

Page 168: A8-24

Advertising
background image

<Appendix 8. Advanced Diagnostics>

A8-24

IM 01C25T02-01E

Relative

Index Index

Parameter Name

Factory Default Write

Mode

Explanation

47

2047 CAP_TEMP_VAL

Measured capsule temperature value and status.

48

2048 CAP_TEMP_RANGE -50.0 to 130.0°C

High and low range limit values, engineering units, decimal point

place for capsule temperature.

49

2049 AMP_TEMP_VAL

Measured Amplifier temperature value and status.

50

2050 AMP_TEMP_RANGE -50.0 to 95.0°C

High and low range limit values, engineering units, decimal point

place for Amplifier temperature.

97

2097 FLG_TEMP_VAL

(Note)

Calculated flange temperature valueand status.

98

2098 FLG_TEMP_RANGE

-50.0 to 130.0°C

High and low range limit values, engineering units, decimal point

place for flange temperature.

99

2099 FLG_TEMP_COEFF

0

AUTO Coefficient to calculate flange temperature.

100

2100 FLG_TEMP_PRI

1

AUTO Priority of the flange temperature alarm. (Not used)

101

2101 FLG_TEMP_H_LIM

130

AUTO Threshold to generate Flg Temp High Alarm.

102

2102 FLG_TEMP_L_LIM

-50

AUTO Threshold to generate Flg Temp Low Alarm.

103

2103 FLG_TEMP_ALM

Status of flange temperature alarm.

Note: The factory default of FLG_TEMP_COEF is 0 so the factory default of FLG_TEMP_VAL indicates the same value as that of

CAP_TEMP_VAL.

A8.3.6 Status Error

There are three statuses of “GOOD”,

“UNCERTAIN”, and “BAD” for the status of FLG_

TEMP_VAL.
The factor that becomes GOOD/UNCERTAIN/BAD

is as follows.

Good: Normal status

Uncertain: Capsule or Amplifier temperature is

out of range

Bad:

• Capsule or Amplifier temperature sensor

failure

• Capsule or Amplifier EEPROM failure

• Resource block or SENSOR Transducer

block is in O/S mode

A8.3.7 Parameter Lists for Heat Trace

Monitoring Function

All the parameters for Heat Trace Monitoring

function belong to the SENSOR Transducer block.