<4. Getting Started>

4-2

IM 01C25T02-01E

NOTE

No CHECK terminal is used for Fieldbus

communication transmitter. Do not connect the

field indicator and check meter.

Before using a Fieldbus configuration tool other

than the existing host, confirm it does not affect the

loop functionality in which all devices are already

installed in operation. Disconnect the relevant

control loop from the bus if necessary.

IMPORTANT

Connecting a Fieldbus configuration tool

to a loop with its existing host may cause

communication data scrambling resulting in a

functional disorder or a system failure.

4.2 Host Setting

To activate Fieldbus, the following settings are

required for the host.

IMPORTANT

Do not turn off the power immediately after

setting. When the parameters are saved to the

EEPROM, the redundant processing is executed

for an improvement of reliability. If the power

is turned off within 60 seconds after setting is

made, the modified parameters are not saved

and the settings may return to the original values.

Table 4.1

Operation Parameters

Symbol

Parameter

Description and Settings

V (ST)

Slot-Time

Indicates the time

necessary for immediate

reply of the device. Unit of

time is in octets (256 μs).

Set maximum

specification for all

devices. For the

transmitter, set a value of

4 or greater.

V (MID)

Minimum-Inter-

PDU-Delay

Minimum value of

communication data

intervals. Unit of time is in

octets (256 μs). Set the

maximum specification

for all devices. For the

transmitter, set a value of

4 or greater.

V (MRD) Maximum-

Reply-Delay

The worst case time

elapsed until a reply is

recorded. The unit is

Slot-time; set the value

so that V (MRD) × V

(ST) is the maximum

value of the specification

for all devices. For the

transmitter, the setting

must be a value of 12 or

greater.

V (FUN) First-Unpolled-

Node

Indicate the address next

to the address range used

by the host. Set 0 × 15 or

greater.

V (NUN) Number-of-

consecutive-

Unpolled-Node

Unused address range.

Not used

0x00

0xF7

0xF8

0x0F

0x10
0x13

0x14

0xFB

0xFC

0xFF

V(FUN)

V(FUN)+V(NUN)

LM device

Bridge device

Unused

V(NUN)

BASIC device

Default address

Portable device address

F0403.ai

Note 1: Bridge device: A linking device which brings data

from one or more H1 networks.

Note 2: LM device: with bus control function (Link Master

function).

Note 3: BASIC device: without bus control function.

Figure 4.2

Available Address Range