4.3 Bus Power ON

4.3.1 Integral Indicator Display When

Powering On

Turn on the power of the host and the bus.
For models with the integral indicator code “D”, the

display shows all segments in the LCD and then

changes to the displays shown below sequentially.

All segments display

Model name (3s)

Communication Protocol (3s)

Device Revision (3s)

F0200.ai

NOTE

LCD display can be set to all segments display

only by changing the following parameter.

LCD Tranceducer Block POWER_ON_INFO

1:ON(Default)

Show all segments display, Model name,

Communication Protocol and device revision

when powering on.

0:OFF

Show all segments display when powering on.

4.3.2 Confirming that Transmitter is

Operating Properly

Turn on the power of the host and the bus. If the

indicator is not lit, check the polarity of the power

supply.
The device information, including PD tag, Node

address, and Device ID, is described on the sheet

attached to the transmitter. The device information

is given in duplicate on this sheet.

DEVICE INFORMATION

Device ID

:

594543000CXXXXXXXX

PD Tag

:

PT2001

Device Revision

:

5

Node Address

:

0xf5

Serial No.

:

XXXXXXXXXXXXXXXXX

Physical Location :

Note:

Our Device Description Files and Capabilities Files available at

http://www.yokogawa.com/fld/ (English) or
http://www.yokogawa.co.jp/fld/ (Japanese)

DEVICE INFORMATION

Device ID

:

594543000CXXXXXXXX

PD Tag

:

PT2001

Device Revision

:

5

Node Address

:

0xf5

Serial No.

:

XXXXXXXXXXXXXXXXX

Physical Location :

Note:

Our Device Description Files and Capabilities Files available at

http://www.yokogawa.com/fld/ (English) or
http://www.yokogawa.co.jp/fld/ (Japanese)

F0404.ai

Figure 4.4

Device Information Sheet Attached to

Transmitter

If no transmitter is detected, check the available

address range and the polarity of the power supply.

If the node address and PD tag are not specified

when ordering, default value is factory set. If two

or more transmitters are connected at a time with

default value, only one transmitter will be detected

from the host as transmitters have the same initial

address. Separately connect each transmitter and

set a different address for each.