<6. Explanation of Basic Items>

6-1

IM 01C25T02-01E

6. Explanation of Basic Items

6.1 Outline

This chapter describes the SENSOR transducer

block, the LCD transducer block, and the AI function

block and explains basic parameter settings.

Refer to Appendixes for other function blocks,

LM function, software download function, and

advanced diagnostics.

6.2 Setting and Changing

Parameters for the Whole

Process

IMPORTANT

Do not turn off the power immediately after

setting. When the parameters are saved to the

EEPROM, the redundant processing is executed

for an improvement of reliability. If the power

is turned off within 60 seconds after setting is

made, the modified parameters are not saved

and the settings may return to the original values.

Block mode
Many parameters require a change of the block

mode of the function block to O/S (Out of Service)

when their data is changed. To change the block

mode of the function block, its MODE_BLK needs

to be changed. The MODE_BLK is comprised of

the four sub-parameters below:

(1) Target (Target mode):

Sets the operating condition of the block.

(2) Actual (Actual mode):

Indicates the current operating condition.

(3) Permit (Permitted mode):

Indicates the operating condition that the

block is allowed to take.

(4) Normal (Normal mode):

Indicates the operating condition that the

block will usually take.

6.3 SENSOR Transducer Block

The SENSOR transducer block is in between the

sensor and the AI function blocks. It calculates

pressure/differential pressure, static pressure,

and capsule temperature from sensor signals.

Then it performs damping and range checks for

the measured values of these three variables and

sends signals to the AI function block.

6.3.1 Functional Block

Figure 6.1 presents the functional block of the

SENSOR transducer. The calculated values

of pressure/differential pressure, H-side static

pressure, L-side static pressure, and capsule

temperature are assigned to PRIMARY_VALUE,

SECONDARY_VALUE, TERTIARY_VALUE, CAP_

TEMP_VAL, AMP_TEMP_VAL, and FLG_TEMP_

VAL (option code: /DG1) respectively. Measured

values output to the AI function blocks are selected

by the Channel parameter of those blocks.

F0601.ai

PRIMARY_VALUE

(Channel1)

Sensor

signals

SECONDARY_VALUE

(Channel2)

TERTIARY_VALUE

(Channel3)
CAP_TEMP_VAL

(Channel4)

Pressure

/differential

pressure

calculation

Static

pressure

calculation

Damping

processing

Damping

processing

Range

check

Range

check

Range

check

Adjust-

ment

Adjust-

ment

Unit

Check

Unit

Check

H-side

static

pressure

L-side

static

pressure

Unit

Check

Capsule

temperature

calculation

AMP_TEMP_VAL

(Channel5)

Range

check

Unit

Check

Amplifier

temperature

calculation

Historical

records

Equipment

information

FLG_TEMP_VAL

(Channel6)

Range

check

Unit

Check

Flange

temperature

calculation

Figure 6.1

SENSOR Transducer Functional Block