2 block mode, Block mode -2 – Yokogawa EJX930A User Manual

Page 43

Advertising
background image

<6. Explanation of Basic Items>

6-2

IM 01C25T02-01E

6.3.2 Block Mode

The Block modes permitted for the SENSOR

transducer block are Automatic (Auto) and Out of

Service (O/S). The mode must be set to Auto under

normal operating conditions, and to O/S when

making changes to an important parameter. For

parameters that can only be changed in the Auto

and O/S modes, refer to the parameter list for the

SENSOR Transducer block in Chapter 9.

6.3.3 Functions Relating to Pressure/

Differential Pressure

Reference to pressure/differential pressure

value:

By accessing PRIMARY_VALUE, it is possible to

refer to the pressure/differential pressure value

and status. The update period of this value is 100

mseconds. The pressure unit is selected by XD_

SCALE.unit of the AI block, in which PRIMARY_

VALUE is selected. The status is normally Good-

Non Specific. However, in the case of a sensor

failure or out of measurement range, it turns to Bad

or Uncertain. For details, refer to Table 8.9.

Setting of signal damping for pressure/

differential pressure:

When the pressure/differential pressure signal

fluctuates greatly, the fluctuation can be reduced

by increasing the time constant for signal damping.

PRIMARY_VALUE_FTIME is the parameter for

setting the signal damping for pressure/differential

pressure. The unit of signal damping is second.

Determination of the range limit of pressure/

differential pressure signal:

When the pressure/differential pressure signal

deviates more than 10% from the capsule

measurement range shown in PRIMARY_VALUE_

RANGE, set the status of PRIMARY_VALUE to

Uncertain-Sensor Conversion not Accurate.

Adjustment of pressure/differential pressure

signal:

EJX Series Pressure/Differential Pressure

Transmitters have been accurately adjusted

according to the specifications at factory setting.

Minimal errors can occur due to the environment

where the transmitter is installed and the mounting

position. To fine-tune any errors, three zero/span

adjustment functions can be used: automatic and

manual zero/span adjustment by communication

terminals, and zero-point adjustment by means of

the external adjustment screw on the transmitter.
Automatic adjustment

The value of the pressure exerted on the point

where the adjustment is to be made is assigned

to parameters (CAL_POINT_LO, CAL_POINT_

HI). After this assignment is set, the amount of

adjustment is calculated by the transmitter and

automatically updated.
Manual adjustment

From the exerted pressure and the output of the

transmitter, calculate the amount of zero/span

adjustment manually, and assign the calculated

value to parameters (CAL_DEVIATION_LO,

CAL_DEVIATION_HI).
Zero-point adjustment by the external screw.

With pressure being exerted on the point where

the adjustment is to be made, zero adjustment

needs to be performed. To do this, adjust the

calculated value by turning the external Zero-point

adjustment screw, so that it agrees with the actual

input pressure (true value). The output value

increases when the screw is rotated to the right. It

decreases when the screw is rotated to the left. The

adjustment width is small when the rotation speed

is low and large when fast.
When performing zero-point adjustment by the

external screw, EXTERNAL_ZERO_TRIM needs to

be set to “Enable.”

Advertising