<6. Explanation of Basic Items>

6-5

IM 01C25T02-01E

6.3.6 BLOCK_ERR

BLOCK_ERR presents the cause of an error in the

block. The SENSOR transducer block checks the

following causes and sets the relevant bits.

BLOCK_ERR

Bit

Error

Cause

1 other

Differential pressure adjusted

by zero/span adjustment out

of measurement range, Static

pressure adjusted by zero/span

adjustment out of measurement

range

7 other

Pressure sensor failure, Capsule

temperature sensor failure

13 other

Electronic circuit failure

15 Out-of-Service MODE_BLK.Target is O/S

6.3.7 XD_ERROR

XD_ERROR is a parameter that contains codes

for the most significant errors that can occur in the

SENSOR transducer block. The errors of XD_

ERROR supported by transmitter and their causes

are presented in the table below. When multiple

errors occur and their error codes are different, the

error with a larger code value is stored first.

XD_ERROR

Bit

Error

Cause

15 Out of Service Sensor TB is in O/S mode.
18 Calibration

error

An error occurred during

calibration or a calibration error

has been detected.

20 Electronics

Failure

An electronic component has

failed.

22 I/O Failure

An I/O failure has occurred.

6.4 LCD Transducer Block

6.4.1 Outline of the Functions

The LCD transducer block controls alarms and

measured values that are displayed on the integral

indicator. It displays not only OUT signals from the

AI blocks, but also I/O signals of the Installed blocks

on the integral indicator.

6.4.2 Block Mode

The Block modes permitted for the LCD transducer

block are Automatic (Auto) and Out of Service (O/

S). Settings can be changed in the AUTO mode for

this block, except the Block tag parameter.

6.4.3 Display Contents of the Integral

Indicator

The components of the integral indicator are the bar

graph, the title field, the center field for numerical

values, the lower text field, and auxiliary characters.

The contents and meanings of these components

are as follows:

F0604.ai

40.000

37.000

Figure 6.2

Screen Display of the integral indicator

Component

name

Contents

Bar graph

Shows the value displayed in the center

field for numerical values scaled in terms

of percentage.

Center field

for numerical

values

Presents values of inputs and outputs.

While the alarm is on, the alarm number

alternates with the displayed value here.

Lower text

field

Displays tag, parameter name, unit, and

signal status. While the alarm is on, the

alarm contents alternate.

Title field

Depicts the type of the value displayed

on the center field for numerical value.
P

Flashes when pressure/

differential pressure is

displayed.

SP

Flashes when static pressure is

displayed.

T

Flashes when temperature is

displayed.

Auxiliary

characters

%

Flashes when the center field

for numerical values displays a

% value.
Flashes when square root

display is selected.

Key

mark

Flashes when Write Protect is

selected.

Ч10,

Ч100,

Ч1000

Used when the calculated value

displayed in the center field for

numerical values is rounded.