<6. Explanation of Basic Items>

6-7

IM 01C25T02-01E

6.4.5 Procedure to Set the Built-in Display

F0607.ai

Corresponding

decimal point

Engineering Unit
Eng. Unit @ 1/10
Eng. Unit @ 1/100
Eng. Unit @ 1/1000

LCD value

(kPa)

Exponent

2

23.46

2

2.35

2

0.23

2

0.02

Select from Parameter Displays (1-4)

(DISPLAY_SEL)

Select items to be displayed in the lower

text field (INFO_SEL)

Specify whether DISPLAY1, DISPLAY2,

DISPLAY3, or DISPLAY4 should be displayed.

Specify whether tag, parameter, unit, or status

should be displayed.

Select parameters to be displayed from

PARAMETER_SEL listed in Table 6.1.

Written as by 6 characters or 6 characters plus “/”,“.”.(*1)

Written as by 6 characters or 6 characters plus “/”,“.”.(*1)

Specify parameters to be displayed

(PARAMETER_SEL)

Perform ON/OFF setting of the bar graph

(BAR_GRAPH_SELECT)

Set the display period

(DISPLAY_CYCLE)

Time unit: 400mS; When the valve set is “7”, the same
display continues for about 2.8 seconds.

Example display of exponent setting:
The LCD value for exponent setting when the actual pressure
value is 23.4568 kPa and the decimal point selected is 2.

Set an exponent (EXP_MODE)

Set the display contents for the block tag to be

displayed in the lower text field

(DISPLAY_TAG)

Set the display contents

of the unit

(DISPLAY_UNIT)

Select whether the unit to be displayed in the

lower text field should be set to

automatic or on a customized basis

(UNIT_SEL)

CUSTOM is

selected

The display selected by

DISPLAY_SEL needs to

be set

AUTO is

selected

Figure 6.3

Procedures to Set the Built-in Display

*1:

Combination of up to 6 characters of alphanumeric and the symbols of [/], [.] and [ ] (space) are available.

If the other characters are specified, space will be displayed.

The symbols of [/] and [.] cannot be specified on the head of a string.