<9. Parameter Lists>

9-1

IM 01C25T02-01E

9. Parameter Lists

Note: The Write Mode column contains the modes in which each parameter is write enabled.

O/S: Write enabled in O/S mode.

MAN: Write enabled in Man mode and O/S mode.

AUTO: Write enabled in Auto mode, Man mode, and O/S mode.

9.1 Resource Block

Relative

Index Index

Parameter Name

Factory Default

Write

Mode

Explanation

0

1000

Block Header

TAG:“RS”

Block

Tag

=O/S

Information on this block such as Block Tag, DD Revision,

Execution Time etc.

1

1001

ST_REV

The revision level of the static data associated with the

resource block. The revision value is incremented each time a

static parameter value in this block is changed.

2

1002

TAG_DESC

Null

AUTO

The user description of the intended application of the block.

3

1003

STRATEGY

0

AUTO

The strategy field can be used to identify grouping of blocks.

This data is not checked or processed by the block.

4

1004

ALERT_KEY

0

AUTO

The identification number of the plant unit. This information

may be used in the host for sorting alarms, etc.

5

1005

MODE_BLK

AUTO

AUTO

The actual, target, permitted, and normal modes of the block.

6

1006

BLOCK_ERR

This parameter reflects the error status associated with the

hardware or software components associated with a block. It is

a bit string, so that multiple errors may be shown.

7

1007

RS_STATE

State of the resource block state machine.

8

1008

TEST_RW

Null

AUTO

Read/write test parameter-used only for conformance testing

and simulation.

9

1009

DD_RESOURCE

Null

String identifying the tag of the resource which contains the

Device Description for this resource.

10

1010

MANUFAC_ID

0x00594543

Manufacturer identification number-used by an interface device

to locate the DD file for the resource.

11

1011

DEV_TYPE

EJX:12

EJA:17

Manufacturer’s model number associated with the

resourceused by interface devices to locate the DD file for the

resource.

12

1012

DEV_REV

EJX:5

EJA:1

Manufacturer revision number associated with the

resourceused by an interface device to locate the DD file for

the resource.

13

1013

DD_REV

1

Revision of the DD associated with the resource-used by an

interface device to locate the DD file for the resource.

14

1014

GRANT_DENY

0

AUTO

Options for controlling access of host computer and local

control panels to operating, tuning and alarm parameters of the

block.

15

1015

HARD_TYPES

Scalar input

The types of hardware available as channel numbers.

bit0: Scalar input

bit1: Scalar output

bit2: Discrete input

bit3: Discrete output

16

1016

RESTART

Allows a manual restart to be initiated. Several degrees of

restart are possible.

1: Run:Run

2: Resource:Restart resource

3: Defaults:Restart with initial value specified in FF functional

spec.(*1)

4: Processor: Restart processor

*1: FF-891 Foundation

TM

Specification Function Block

Application Process Part 2.

17

1017

FEATURES

Reports

Fault state

Soft W Lock

Hard W Lock

Multi_bit Alarm

support

Used to show supported resource block options.