2 sensor transducer block, Sensor transducer block -5 – Yokogawa EJX930A User Manual

Page 69

Advertising
background image

<9. Parameter Lists>

9-5

IM 01C25T02-01E

Relative

Index Index

Parameter Name

Factory Default

Write

Mode

Explanation

119

1119

DEVICE_

CONDITION_

ACTIVE_4

0x00000000

FD_EXTENDED_ACTIVE_4 & FD_EXTENDED_MAP_4

120

1120

DEVICE_

CONDITION_

ACTIVE_5

0x00000000

FD_EXTENDED_ACTIVE_5 & FD_EXTENDED_MAP_5

121

1121

DEVICE_

CONDITION_

ACTIVE_6

0x00000000

FD_EXTENDED_ACTIVE_6 & FD_EXTENDED_MAP_6

122

1122

DEVICE_

CONDITION_

ACTIVE_7

0x00000000

FD_EXTENDED_ACTIVE_7 & FD_EXTENDED_MAP_7

123

1123

DEVICE_

CONDITION_

ACTIVE_8

0x00000000

FD_EXTENDED_ACTIVE_8 & FD_EXTENDED_MAP_8

9.2 SENSOR Transducer Block

Relative

Index Index

Parameter Name

Factory Default Write

Mode

Explanation

0

2000

Block Header

TAG: “STB”

Block

Tag =

O/S

Information on this block such as Block Tag, DD Revision,

Execution Time etc.

1

2001

ST_REV

The revision level of the static data associated with the function

block. The revision value will be incremented each time a static

parameter value in the block is changed.

2

2002

TAG_DESC

Null

AUTO The user description of the intended application of the block

3

2003

STRATEGY

1

AUTO The strategy field can be used to identify grouping of blocks.

This data is not checked or processed by the block.

4

2004

ALERT_KEY

1

AUTO The identification number of the plant unit. This information

may be used in the host for sorting alarms, etc.

5

2005

MODE_BLK

AUTO

AUTO The actual, target, permitted, and normal modes of the block.

6

2006

BLOCK_ERR

This parameter reflects the error status associated with

hardware or software components associated with a block. It is

a bit string, so that multiple errors may be shown.

7

2007

UPDATE_EVT

This alert is generated by any change to the static data.

8

2008

BLOCK_ALM

The block alarm is used for all configuration, hardware,

connection failure or system problems in the block. The cause

of the alert is entered in the subcode field. The first alert to

become active will set the Active status in the Status attribute.

9

2009

TRANSDUCER_

DIRECTORY

A directory that specifies the number and starting indices of the

transducers.

10

2010

TRANSDUCER_

TYPE

100 (Standard

Pre-ssure with

Calibration)

Identifies transducer.

11

2011

XD_ERROR

The error code in transducer.

0=No failure

18=Calibration error

20=Electronics failure

22=I/O failure

12

2012

COLLECTION_

DIRECTORY

A directory that specifies the number, starting indices, and DD

Item Ids of the data collections in each transducer within a

transducer block.

13

2013

PRIMARY_ VALUE_

TYPE

107: differential

pressure

108: gauge

pressure

109: absolute

pressure

O/S

The type of measurement represented by primary value.

Followings are available for the transmitter:

107=differential pressure

108=gauge pressure

109=absolute pressure

14

2014

PRIMARY_ VALUE

The measured value and status available to the function block.

15

2015

PRIMARY_ VALUE_

RANGE

Range of capsule —

The High and Low range limit values, engineering units code

and the number of digits to the right of the decimal point to be

used to display the primary value.

16

2016

CAL_POINT_HI

Max range

O/S

The highest calibrated value.

17

2017

CAL_POINT_LO

0

O/S

The lowest calibrated value.

Advertising