<Appendix 1. Signal Characterizer (SC) Block>

A1-2

IM 01C25T02-01E

Y

or

X

X or Y

Input section

Line-segment factor

determination section

Output section

IN_1

Determining

the mode

Determining

the gradient

and intercept

Determining the

status and

computing OUT

OUT

processing

BLOCK_ERR

FA0102.ai

IN_2

CURVE_X

CURVE_Y

SWAP_2

OUT_1

OUT_2

MODE = AUTO

MODE = MAN or O/S

Figure A1.2 Overview of the Signal Characterizer Block

The following describes the Signal Characterizer

block, dividing its functions into three sections:

• Input section: Determines the mode and judges

BLOCK_ERR.

• Line-segment factor determination section:

Determines the gradient and intercept for

OUT_1 and

OUT_2 based on CURVE_X, CURVE_Y, and

SWAP_2 at shift .

• Output section: Multiplies the input values in

IN_1 and IN_2 by the gradient and adds the

intercept to them before outputting the results.

Alternatively, it outputs a limit value.

A1.2 Input Section

The input section determines the mode and judges

BLOCK_ERR.

A1.2.1 Determining the Mode

The following describes operations of the Signal

Characterizer block.

Supported Mode

Rules

O/S

(Out of Service)

• System-stopped status

• Configuration change

Man

• If you do not want to output the

value and the status from IN, you

can manually transmit the value to

OUT.

Auto

• Automatic system operation status

A1.2.2 Judging BLOCK_ERR

BLOCK_ERR indicates the cause of an error in the

function block. If the cause of an error indicated by

BLOCK_ERR occurs, the following configuration

error is generated.

Name

Description

Block

Configuration

Error

1) “–INFINITY” has been configured for

CURVE_X and CURVE_Y.

2) “+INFINITY” has been configured for

X1 of CURVE_X.

3) “+INFINITY” has been configured for

Y1 of CURVE_Y.

4) A value of the array of CURVE_X

does not increase in a monotone

manner.

5) A configuration error when SWAP_2

is on

• A value of the array of CURVE_Y

does not increase or decrease in a

monotone manner.

6) The value of SWAP_2 is any value

other than 1 or 2.

The mode changes to O/S if a block configuration

error occurs.