<Appendix 1. Signal Characterizer (SC) Block>

A1-3

IM 01C25T02-01E

A1.3 Line-segment Factor Determination Section

When the mode is AUTO and no bit in BLOCK_ERR is set, the "gradient" and "intercept" of a line passing

through two points that are considered line-segment approximation values are determined.

A1.3.1 Conditions for Configuring Valid Coefficients (CURVE_X, CURVE_Y)

No write error is generated with respect to the settings in CURVE_X and CURVE_Y. However, a configuration

error occurs in the following cases:
1. "+INFINITY" has been configured for X1 or Y1.

2. "–INFINITY" has been configured for each X or Y.

3. The values of CURVE_X are not increasing in a monotone manner (X1 < X2 < ... < X20 < X21).

(If SWAP_2 is off, it is acceptable if the values of CURVE_Y do not increase or decrease in a monotone

manner.)

4. The values of CURVE_Y are not increasing or decreasing in a monotone manner when SWAP_2 is on.
If a configuration error occurs, the Block Configuration Error bit in BLOCK_ERR is set, causing the mode to

change to O/S.

Example of the case where SWAP_2 is off:

Y

Output

Y6

(High limit)

Y1

(Low limit)

X1

X2

X3

X4

X5

X6

X7 =INFINITY

X
Input

FA0103.ai

Figure A1.3 Example of Curve (SWAP_2 = off)

The range of CURVE_X: X1 to X6 (X7 and above are invalid because "+INFINITY" has been configured for

X7*

1

.)

The X1 to X6 values always increase in a monotone manner (X1 < X2 < X3 < X4 < X5 < X6).
If an input value is smaller than X1, it is set to Y1.
If an input value is larger than X6, it is set to Y6.
The range of CURVE_Y: Y1 to Y6
It is acceptable if the Y1 to Y6 values do not increase in a monotone manner.
However, if the setting of SWAP_2 is changed from off to on, the values of CURVE_Y must increase or

decrease in a monotone manner. Thus, if a value of CURVE_Y does not increase or decrease in a monotone

manner in this setting, the mode changes to O/S, causing the Block Configuration Error bit in BLOCK_ERR to

be set.

*1: For any points of the curve that are not used, configure "+INFINITY" for all of them.