<Appendix 1. Signal Characterizer (SC) Block>

A1-7

IM 01C25T02-01E

A1.5.3 Backward Control

SC: The controlled variable output from PID is

converted into an information quantity that can be

interpreted by AO, and backward information from

AO is converted into an information quantity that

can be interpreted by PID before being transmitted

to the PID.

AI

OUT

AO

CAS_IN

SC

OUT_2

OUT_1

IN_1

IN_2

PID

BKCAL_IN

OUT

IN

BKCAL_OUT

SWAP_2=ON

FA0110.ai

Figure A1.10 Backward Control (SWAP_2 = On)

To enable backward control (which inverts the X

and Y axes), the line-segment function must be

set so that the elements of the curve increase in a

monotone manner.(As shown in Figure A1.11) If

they do not increase in a monotone manner, the

mode changes to O/S, disabling calculation.

No.

CURVE_X

CURVE_Y

1

5

5

2

10

10

3

15

11

4

20

20

5

25

25

6

30

26

7

35

30

8

40

40

9

45

45

10

50

50

11

51

51

12

52

54

13

53

59

14

54

66

15

55

75

16

65

80

17

75

81

18

80

85

19

85

86

20

90

90

21

95

95

100

90

80

70

60

50

40

30

20

10

0

10 20

30 40

50

60 70

80

90 100

FA0111.ai

Line-segment function

C

U

R

VE

_Y

CURVE_X

X_RANGE = 100, 0, %, 0x00

Y_RANGE = 100, 0, %, 0x00

Figure A1.11 Setting Example of a Line-segment

Function