Appendix 2. integrator (it) block, A2.1 schematic diagram of integrator block, A2.1 – Yokogawa EJX930A User Manual

Page 85: A2-1

Advertising
background image

<Appendix 2. Integrator (IT) Block>

A2-1

IM 01C25T02-01E

Appendix 2. Integrator (IT) Block

The Integrator (IT) block adds two main inputs and integrates them for output. The block compares the

integrated or accumulated value to TOTAL_SP and PRE_TRIP and generates discrete output signals OUT_

TRIP or OUT_PTRIP when the limits are reached.
The output is as represented by the following equation (for counting upward and rate conversion).

OUT.Value = Integration start value + Total

Total = Total + Current Integral

Current Integral = (x + y) × Δt

x: IN_1 value whose unit has been converted

y: IN_2 value whose unit has been converted

Δt: block execution period

A2.1 Schematic Diagram of Integrator Block

The following shows the schematic diagram of the Integrator block.

OUT

–1

TIME_UNIT2

PULSE_VAL2

–1

UNIT_CONV

OP_CMD_INT

(RESET)

INTEG_OPTS

(CARRY)

Reverse

Forward

Forward

OUT_PTRIP

OUT_TRIP

INTEG_OPTS

(FROW TYPE)

Add

Compare

Compare

TOTAL / RTOTAL

Integrate

INTEG_TYPE

INTEG_OPTS (QUALITY)

GOOD_LIM

UNCERT_LIM

CLOCK_PER

N_RESET

MAN

MAN

MAN

Convert Rate

Convert Accum

Convert Rate

Convert Accum

TOTAL_SP

PRE_TRIP

INTEG_OPTS

(INPUT TYPE)

PULSE_VAL1

TIME_UNIT1

INTEG_OPTS

(INPUT TYPE)

Reverse

FA0201.ai

IN_1

RESET_IN

REV_FLOW1

IN_2

REV_FLOW2

RESET_CONFIRM

IN_1: Block input 1 (value and status)

IN_2: Block input 2 (value and status)

REV_FLOW1: Indicates whether the sign of IN_1 is reversed. It is a discrete signal.

REV_FLOW2: Indicates whether the sign of IN_2 is reversed. It is a discrete signal.

RESET_IN: Resets the integrated values. It is a discrete signal.

RESET_CONFIRM: Reset confirmation input. It is a discrete signal.

OUT: Block output (value and status)

OUT_PTRIP: Set if the target value exceeds PRE_TRIP. It is a discrete signal.

OUT_TRIP: Set if the target value exceeds TOTAL_SP (or 0). It is a discrete signal.

The Integrator block is classified into the following five sections for each function:

• Input process section: Determines the input value status, converts the rate and accumulation, and

determines the input flow direction.

• Adder: Adds the two inputs.

• Integrator: Integrates the result of the adder into the integrated value.

• Output process section: Determines the status and value of each output parameter.

• Reset process section: Resets the integrated values.

Figure A2.1 Integrator Block