<Appendix 2. Integrator (IT) Block>

A2-5

IM 01C25T02-01E

Table A2.1 INTEG_TYPE

Name

Integration

Method

Integration Range

Reset Trigger (Reset if one of the

following conditions is established)

Trip Output

UP_AUTO(1) Counting up

Starting from "0"

-INF< Total <TOTAL_SP

0< ATotal <+INF

0< RTotal <+INF

-INF< AccTotal <+INF

• OUT reaches TOTAL_SP.

• RESET_IN = 1

• OP_CMD_INT = 1

UP_DEM(2)

Counting up

Starting from "0"

-INF< Total <+INF

0< ATotal <+INF

0< RTotal <+INF

-INF< AccTotal <+INF

• RESET_IN = 1

• OP_CMD_INT = 1

DN_AUTO(3)

Counting down

Starting from

TOTAL_SP

0< Total <+INF

0< ATotal <+INF

0< RTotal <+INF

-INF< AccTotal <+INF

• OUT reaches "0."

• RESET_IN = 1

• OP_CMD_INT = 1

DN_DEM(4)

Counting down

Starting from

TOTAL_SP

-INF< Total <+INF

0< ATotal <+INF

0< RTotal <+INF

-INF< AccTotal <+INF

• RESET_IN = 1

• OP_CMD_INT = 1

PERIODIC(5) Counting up

Starting from "0"

-INF< Total <+INF

0< ATotal <+INF

0< RTotal <+INF

-INF< AccTotal <+INF

• At the period specified by

CLOCK_PER

• OP_CMD_INT = 1

×

DEMAND(6)

Counting up

Starting from "0"

-INF< Total <+INF

0< ATotal <+INF

0< RTotal <+INF

-INF< AccTotal <+INF

• RESET_IN = 1

• OP_CMD_INT = 1

×

PER&DEM(7) Counting up

Starting from "0"

-INF< Total <+INF

0< ATotal <+INF

0< RTotal <+INF

-INF< AccTotal <+INF

• At the period specified by CLOCK_PER

• RESET_IN = 1

• OP_CMD_INT = 1

×

Legend

: Trip output is made.

×

: No trip output is made.

A2.5 Output Process

There are the following three output parameters:

1. OUT

2. OUT_TRIP

3. OUT_PTRIP

Parameters OUT_TRIP and OUT_PTRIP are used only when INTEG_TYPE is a value from 1 to 4.

A2.5.1 Status Determination

The same criteria for determining the status of the output of the Integrator block are used in common for the

above three parameters.

0%

UNCERT_LIM

GOOD_LIM

100%

PCT_INCL

GOOD

Uncertain

Bad

PCT_INCL=100×(1 - (msp of RTotal)/(msp of ATotal))

msp of RTotal: RTotal value that is converted into a short floating-point number

msp of ATotal: ATotal value that is converted into a short floating-point number

RTotal: Integrated value of the absolute values of the increments whose status is bad

ATotal: Integrated value of the absolute values of the increments regardless of the output status

FA0204.ai

Figure A2.4 Status of OUT, OUT_TRIP, and OUT_PTRIP Outputs