<Appendix 2. Integrator (IT) Block>

A2-6

IM 01C25T02-01E

OUT.Value, OUT_TRIP.Status, and OUT_PTRIP.Status are determined by the ratio of the "Good" integrated

values to all integrated values, which is stored in PCT_INCL (0% to 100%). The user must set the threshold

value of each status to UNCERT_LIM and GOOD_LIM.
The Integrator block determines the status of the output using the three parameters: PCT_INCL,
UNCERT_LIM, and GOOD_LIM.

● PCT_INCL ≥ GOOD_LIM

Good

● UNCERT_LIM ≤ PCT_INCL < GOOD_LIM

Uncertain

● PCT_INCL < UNCERT_LIM

Bad

If INTEG_TYPE is 5, 6, or 7, the status of the trip output becomes "Good-NS-Constant."

A2.5.2 Determining the Output Value

The value of OUT.Value is determined as follows:

● For counting up

OUT = integration start value (0) + Total

● For counting down

OUT = integration start value (TOTAL_SP) _ Total

Total: Total of integrated values. This value is retained even if INTEG_TYPE is changed during integration

(in AUTO).

If OUT is rewritten in the MAN mode, integration starts with the value rewritten in MAN mode after the mode

was returned to AUTO.
The values in OUT_TRIP and OUT_PTRIP are determined according to the correlation between OUT and

TOTAL_SP/PRE_TRIP.

Counting up starting from 0

• For counting up

PRE_TRIP(#31)

OUT_TRIP(#14):0

OUT_PTRIP(#15):1

• For counting down

Counting down starting from TOTAL_SP

PRE_TRIP(#31)

0

0

TOTAL_SP(#7)

TOTAL_SP(#7)

FA0205.ai

OUT_TRIP(#14):0

OUT_PTRIP(#15):1

OUT_TRIP(#14):0

OUT_PTRIP(#15):0

OUT_TRIP(#14):1

OUT_PTRIP(#15):1

OUT_TRIP(#14):0

OUT_PTRIP(#15):0

OUT_TRIP(#14):1

OUT_PTRIP(#15):1