<Appendix 2. Integrator (IT) Block>

A2-8

IM 01C25T02-01E

When OP_CMD_INT has become "H" and a reset was made, OP_CMD_INT automatically returns to "L."

Even if RESET_IN becomes "H," activating a reset, RESET_IN does not automatically return to "L."

The RESET_IN setting will not be retained if the power is turned OFF.

A2.6.2 Reset Timing

All items are reset during execution of the function block. Therefore, the minimum period of a reset is the block

execution period.

● 5-second rule
If a reset is made, the next reset will not be accepted for 5 seconds after that.

Even if UP_AUTO (or DN_AUTO) is activated and TOTAL_SP (or 0) is reached within 5 seconds, the next

reset will not be made for 5 seconds from the previous reset.
● CLOCK_PER
If INTEG_TYPE is PERIODIC (5) or PER&DEM (7), a reset is made at the period (sec) set to the CLOCK_PER

parameter.

If the value in CLOCK_PER is smaller than the function block's execution period, bit 1 of BLOCK_ERR "Block

Configuration Error" is set.

A2.6.3 Reset Process

The basic reset process sequence is as follows:

1.) Snapshot
2.) Clearing the integrated values
3.) Reset count increment
4.) Judging OUT_TRIP and OUT_PTRIP (see A2.5)

1.) Snapshot
Saves the following values in the specified parameters before clearing the integrated values. These values will

be retained until the next reset is made.

STOTAL = Total

SRTOTAL = RTotal

SSP = TOTAL_SP

2.) Clearing the integrated values
The reset process clears the Total, ATotal, and RTotal values in the internal registers.

Total = 0

ATotal = 0

RTotal = 0

3.) Reset count increment
Each time a reset is made, the N_RESET parameter will be incremented.

The high limit is 999,999, and if this limit is exceeded, the count returns to "0."