A2.7 list of integrator block parameters, A2.7, A2-9 – Yokogawa EJX930A User Manual

Page 93

Advertising
background image

<Appendix 2. Integrator (IT) Block>

A2-9

IM 01C25T02-01E

4.) Judging OUT_TRIP and OUT_PTRIP (see A2.5)
OUT_TRIP and OUT_PTRIP are judged again on the basis of the cleared integrated values.
There are two options relating to a reset:

i Confirm reset (bit 8 of INTEG_OPTS)

ii Carry (bit 6 of INTEG_OPTS)

i Confirm reset (bit 8 of INTEG_OPTS)

If this option is enabled, the next reset is rejected until "1" is set to RESET_CONFIRM.

ii Carry (bit 6 of INTEG_OPTS)

If this option is enabled while INTEG_TYPE is UP_AUTO or DN_AUTO, the value exceeding the threshold

at a reset will be carried into the next integration.

If INTEG_TYPE is any setting other than UP_AUTO or DN_AUTO, this option is irrelevant.

A2.7 List of Integrator Block Parameters

Index

Parameter

Name

Initial

Value

Write

Mode

View

Definition

1 2 3 4

0

BLOCK_

HEADER

TAG:“IT”

Block

Tag=O/S

Information relating to this function block, such as block tag, DD revision,

execution time

1

ST_REV

0

---

2 2 2 2 The revision level of the set parameters associated with the Integrator

block

2

TAG_DESC

Null

Stores comments describing tag information.

3

STRATEGY

1

2 The strategy field is used by a high-level system to identify the function

block.

4

ALERT_KEY

1

1 Key information used to identify the location at which an alert occurred

5

MODE_BLK

4

4

Integrator block mode. O/S, MAN, and AUTO are supported.

6

BLOCK_ERR

---

2

2

Indicates the active error conditions associated with the function block in

bit strings.

7

TOTAL_SP

1000000.0

4

4

The setpoint of an integrated value or a start value for counting down

8

OUT

MAN

5

5

The block output

9

OUT_RANGE 1000000.0

11

Set scaling for output display. This does not affect operation of the function

block.

It is used for making memos.

0.0

m3 (1034)

0

10

GRANT_DENY

0

2

The parameter for checking if various operations have been executed

11

STATUS_

OPTS

0

O/S

2 Allows you to select a status-related option.

The Integrator block uses "Uncertain if Man mode" only.

12

IN_1

0.0

5

5

Inputs flow (Rate, Accum) signals from the AI block or PI block.

13

IN_2

0.0

5

5

14

OUT_TRIP

0

2

2

An output parameter informing the user that the integrated value has

exceeded the setpoint

15

OUT_PTRIP

0

2

2

An output parameter informing the user that the integrated value is

reaching the setpoint

16

TIME_UNIT1

second (1)

MAN

1

Set the time unit of the rate (kg/s, lb/min, kg/h ... etc.) of the corresponding

IN.

17

TIME_UNIT2

second (1)

MAN

1

18

UNIT_CONV

1.0

4 Specify the unit conversion factor for standardizing the unit of IN_2 into

that of IN_1.

19

PULSE_VAL1

1.0

MAN

4 Set the factor for converting the number of pulses for the corresponding

IN into an appropriate engineering unit.

20

PULSE_VAL2

1.0

MAN

4

21

REV_FLOW1

0

2

2

Selector switch used to specify the fluid flow direction (forward/reverse)

with respect to the corresponding IN

22

REV_FLOW2

0

2

2

23

RESET_IN

0

2

2

The parameter that receives a reset request from an external block to

reset the integrated values

24

STOTAL

0.0

4

Indicates the snapshot of OUT just before a reset.

25

RTOTAL

0.0

MAN

4

4

Indicates the integrated value of the absolute values of the increments if

the input status is "Bad."

26

SRTOTAL

0.0

4

Indicates the snapshot of RTOTAL just before a reset.

27

SSP

0.0

4

Indicates the snapshot of TOTAL_SP just before a reset.

Advertising