A3.2 Input Section

A3.2.1 Mode Handling

The Input Selector block’s operations are determined by the mode (parameter name: MODE_BLK). The

following describes operations in each mode.

Supported Mode

Role

O/S

(Out of Service)

· System-stopped status.

· Allows you to make changes to configuration.

Man

· If you do not want to output the value and status from IN or if the

value or status thus output is not preferable, you can manually

transmit the value to OUT.

Auto

· Automatic system operation status.

Valid Input

When the following conditions are satisfied, the value of IN_n becomes valid.
1) The QUALITY in each status of IN_n is either Good (NC), Good (C), or Uncertain*

1, 3

.

2) The values of DISABLE_n corresponding to each IN_n are OFF and the QUALITY in the status of which is

either Good (NC), Good (C), or Uncertain*

1, 2

.

3) The number of inputs that are “good” is greater than the value of MIN_GOOD*

4

.

Note:

*1:

Uncertain is applicable when “Use Uncertain as Good” is selected in the STATUS_OPTS parameter.

*2:

If the status of DISABLE_n is Bad or Uncertain, its quality is lower so that the status of IN_n is also defined as lower quality. When

DISABLE_n is ON, the value of IN_n becomes invalid. For the priority of DISABLE_n is higher than that of IN_n.

Status in SELECT_TYPE except OP_SELECT

QUALITY of DISABLE / IN Status

IN

Good (NC)

Valid

Good (C)

Valid

Uncertain

*1

Valid

Uncertain

Invalid

Bad

Invalid

Condition: The number of inputs that are “good” is greater than the value of MIN_GOOD.

*3:

Priority of IN_n when the same value is input.

Priority

1:Highest

8:Lowest

Input

1

IN_1

2

IN_2

3

IN_3

4

IN_4

5

IN_5

6

IN_6

7

IN_7

8

IN_8

*4:

Refer to A3.2.2 for the details of MIN_GOOD.