4.INSTALLATION

IM 1E8B0-01E

4-19

4.4.6 Connecting to External Instruments

All the devices to be connected to current output and pulse output must be
conformed to CSA1010, CSA950, IEC1010 or IEC950.

(1) Analog Signal Output (4 to 20mA DC signal is output)

ADMAG CA

Receiving instrument

Load resistance max 750

(max 600

for BRAIN

Communication)

Figure 4.4.4

Connection for Analog Signal Output

(2) Pulse Output

This is a transistor contact (insulated type) so attention must be paid to
voltage and polarity when making connections.

• In case of the constant of inputfilter of Electric Counter is more than the

pulse width, it makes signal decreases and can't calculate correctly.

• In case of input impedance of Electric Counter is large, inductive noise

from power supply bring bad influence to it. To calculate correctly, it is
recommended to use sealed cable or to make input impedance small
enough within the limits of pulse output of Magnetic Flowmeter.

ADMAG CA

PULSE OUT

P+

P–

Protective diode

Mechanical counter

ADMAG CA

PULSE OUT

P+

P–

Universal counter or Electronic counter

Load

30 V DC, 0.2A max.

Figure 4.4.5

Pulse Output Connection