2 zero adjustment via the bt200, Zero adjustment via the bt200 -3 – Yokogawa ADMAG CA User Manual

Page 68

Advertising
background image

IM 1E8B0-01E

8-3

8. ACTUAL OPERATION

8.1.2 Zero Adjustment Via the BT200

Setting displayed

Description

Call up the menu screen and select "C:ADJUST"

Press the ENTER key to call the screen displaying the parameter sub items. Move
the inverse video bar to C02:MAGFLOW ZERO

Pressing the ENTER key causes the data setup screen to be displayed. If the
security screen is displayed, enter the security code.

While "C02:MAGFLOW ZERO" is displayed, press the ENTER key once, then
wait a few seconds and press again.
"AUTO ZERO" is now displayed

After about 60 seconds, press the "F4" of the Function key causes the Menu screen
to be displayed. The zero correction is displayed. Then the meter returns to data
display mode.

CLR

DATA

DATA

MENU
A:DISPLAY
B:SET

C:ADJUST

D:DISP SEL
E:TOTAL SET
F:PULSE SET

ESC

SET

ADJ

DIAG

HOME

PARAM
C01:ZERO TUNING
ENABLE

C02:MAGFLOW ZERO

0 .05
C60:SELF CHECK
GOOD

ESC

DIAG

CLR

DATA

SET
C02:MAGFLOW ZERO
0.05
+ 00.05

ESC

DIAG

DIAG

SET
C02:MAGFLOW ZERO
AUTOZERO

OK

NO

FEED

DIAG

PARAM
C01:ZERO TUNING
ENABLE

C02:MAGFLOW ZERO

0 .02
C60:SELF CHECK
GOOD

ESC

DATA

*For entry of the security code, see IM ICA11-0IE