3 unit setting, 4 range setting, 5 setting damping time constant – Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 13: 6 tag number and memo writing, Unit setting -6, Range setting -6, Setting damping time constant -6, Tag number and memo writing -6, A) changing the range with keypad

Advertising
background image

IM 01C50T03-01E

3-6

3. OPERATION

3.2.3

Unit Setting

B11: PV UNIT, B21: SV UNIT, B31: TV UNIT, B41: 4V

UNIT

Select the engineering unit for the process variables
assigned as PV, SV, TV, and 4V from degree C,
Kelvin, degree F* and degree R*. When mV or ohm is
specified as an input type, the unit is automatically set
to mV or ohms.

*:

Degree F and degree R are available only when
optional code /D2 is specified.

3.2.4

Range Setting

(a) Changing the range with keypad

Lower range value setting;

F10: LRV, Upper range value setting; F20: URV

The range for the PV corresponding to the 4 to 20mA
output signal is set at the factory before shipment. The
procedure to rerange is as follows.

F0304.EPS

DATA

DIAG

PRNT

ESC

PARAM
F10:LRV
0 degC
F20:URV
100 degC
F30:AUTO LRV
DISABLE

DEL

CLR

ESC

PARAM
F20:URV
0 degC
+ 150

1. Select F20: URV and press

[ENTER].

2. Input “150” and press [ENTER]

twice.

3. Press [OK].

Note : The unit selected in B11: PV UNIT is applied to the units used

for F10 and F20.

Example: Changing the measurement range from

0 to 100

°

C to 0 to 150

°

C .

NOTE

When entering numeric values at the range
setting, the value of URV must be greater than
that of LRV.
Range Setting Condition: URV > LRV

(b) Changing the range while applying an

actual input

F30: AUTO LRV

F35: AUTO URV

This feature allows the lower and upper range values to
be setup automatically with the actual input applied.

3.2.5

Setting Damping Time Constant

B12: PV DAMPING, B22: SV DAMPING,

B32: TV DAMPING, B42: 4V DAMPING

Setting the response time of each Process Variable to
make the output change very slowly with a rapid
change in input. Set the value from 0 to 99 seconds.

If the time constant is set to 2 seconds, the transmitter
calculates a reading every cycle using the damping
equation, in order to make the output 63 percent of the
input range after 2 seconds.

This damping time constant is normally set to work
when the temperature make a step change within 2
percent of the output range. The damping can be
changed using the “B13: PV DMP POINT” parameter.

Setting Damping Holding Point

B13: PV DMP POINT

This parameter is used to set the point where the
transmitter conducts the PV damping operation,
depending on a magnitude of the change in the
input value. When the change value in percent
exceeds the setting value, the transmitter outputs
the signal without the damping operation.
Set the value as a percent of span.

Example: Output pattern for the setting value of 10%

Input

Output

Time

3 sec.

9%

(

Њ

C)

10

0

(%)

10

0

Input

Output

Time

3 sec.

(

Њ

C)

10

0

(%)

10

0

14%

F0325.EPS

•Change value less then 10%

•Change value 10% or above

Assumed setting

Renge: 0 to 100

Њ

C

Damping time: 3 sec.

3.2.6

Tag Number and Memo Writing

Tag number

(See Appendix A. Section A.3.2)

C10: TAG NO.

Up to sixteen alphanumeric characters can be entered.
The tag number is as specified upon shipment.

Advertising
This manual is related to the following products: