List of parameters, List of parameters -1 – Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 27

Advertising
background image

IM 01C50T03-01E

5-1

5. LIST OF PARAMETERS

5.

LIST OF PARAMETERS

NO.

Parameter name

Content

R/W

Remarks

Applicable model

UPLOAD DATA

110 310 320 SET ALL

Data initial value

YTA110 YTA310 YTA320

01 MODEL

Model

R

02

TAG No.

Tag number

R

03 SELF

CHECK Self-diagnostics

R

A VARIABLE Variable

R

A10

PV

Primary variable

R

Unit specified in B11

A11

mA of RANGE

Output in mA

R

3.6 to 21.6 mA

A12

% of RANGE

Output in %

R

-2 to 110%

A20

SV

Secondary variable

R

Unit specified in B21

A30

TV

Tertiary variable

R

Unit specified in B31

A40

4V

Fourth variable

R

Unit specified in B41

A50

TERM

Terminal temperature

R

Unit specified in B51

A60 SELF

CHECK Self-diagnostics

R GOOD, ERROR, Lower Output, Upper Output,

Sensor1 Failure, Sensor2 Failure, S1 Signal
Error, S2 Signal Error, Lower Amb TEMP,
Upper Amb TEMP, Sns Backup Start, Illegal PV
MAP, Term Sns Failure, EEPROM Failure, CPU
Failure, AD Conv Failure, Reverse Cal Fail

B

SET VAR CON. Set process variable condition

R

B05

SET DIFF

Set differential direction

W

Sensor1-Sensor2, Sensor2-Sensor1

B10

PV is

PV mapping

W

Sensor1, Sensor2

*

, DIFFERENCE

*

,

AVERAGE

*

, Sensor1-Term, Sensor2-Term

*

,

Terminal

Temp

(

*

item can be selected only with YTA320)

B11

PV UNIT

PV engineering unit

W

degC, kelvin, degF

*4

, degR

*4

B12

PV DAMPING

PV damping time constant

W

0 to 99 seconds

B13

PV DMP POINT PV damping holding point

W

0 to 99%

B20

SV is

SV mapping

W

Sensor1, Sensor2

*

, DIFFERENCE

*

,

AVERAGE

*

, Sensor1-Term, Sensor2-Term

*

,

Terminal Temp Not Used

(

*

item can be selected only with YTA320)

B21

SV UNIT

SV engineering unit

W

degC, kelvin, degF

*4

, degR

*4

B22

SV DAMPING

SV damping time constant

W

0 to 99 seconds

B30

TV is

TV mapping

W

Same as B20

B31

TV UNIT

TV engineering unit

W

degC, kelvin, degF

*4

, degR

*4

B32

TV DAMPING

TV damping time constant

W

0 to 99 seconds

B40

4V is

4V mapping

W

Same as B20

B41

4V UNIT

4V engineering unit

W

degC, kelvin, degF

*4

, degR

*4

B42

4V DAMPING

4V damping time constant

W

0 to 99 seconds

B51

TERM UNIT

Terminal temperature unit

W

degC, kelvin, degF

*4

, degR

*4

B60

SELF CHECK

Self-diagnostics

R

Same as A60

C

SET TAG

Set Tag number

R

C10

TAG NO.

Tag number

W

16 alphanumeric characters

C60

SELF CHECK

Self-diagnostics

R

Same as A60

D SET

SENSOR1

Set

Sensor1

R

D10

SENSOR1 TYPE Sensor1 sensor type

W

TYPE B, E, J, K, L, N, R, S, T, U, W3, W5,
Pt100, Pt200, Pt500, JPt100, Ni120, Cu,
ohm, mV, Non Connection

D20

SENSOR1 WIRE Sensor1 wire connection

W

2 WIRE, 3 WIRE, 4 WIRE

D40

SENSOR1

Sensor1 input value

R

Unit specified in D20

D41

SENSOR1 UNIT Sensor1 engineering unit

W

degC, kelvin, degF

*4

, degR

*4

D50

SNSR1 MATCH Sensor1 RTD sensor matching

W

DISABLE, ENABLE

D51

SNSR1 R0

Sensor1-specific constant (R0)

W

D52

SNSR1 A

IEC co-efficient

W

D53

SNSR1 B

IEC co-efficient

W

D54

SNSR1 C

IEC co-efficient

W

D55

SNSR1 ALPHA

Callendar-Van-Dusen co-efficient A

W

D56

SNSR1 DELTA

Callendar-Van-Dusen co-efficient B

W

D57

SNSR1 BETA

Callendar-Van-Dusen co-efficient C

W

D60

SELF CHECK

Self-diagnostics

R

Same as A60

YTA110 YTA310 YTA320

Specified upon order

GOOD

Operation

Operation

Operation

Operation

Operation

Operation

Operation

GOOD

Sensor1-Sensor2

Sensor1

degC

2 seconds

2 %

Not Used

degC

2 seconds

Not Used

degC

2 seconds

Not Used

degC

2 seconds

degC

GOOD

Specified upon order

GOOD

Pt100

3 WIRE

Operation

degC

DISABLE

+100

+3.9083 E-3

-5.7749 E-7

-4.183 E-12

+3.8505 E-3

+1.4998 E0

+1.0862 E-1

GOOD

*

1:

indicates parameters which may be displayed depending on the setting for other parameters.

indicates parameters available on the model with optional code /CM1.

*

2: RW: R = Read only, W = Read & Write

*

3: Indicates the parameter selected by H30: UPLOAD SELCT.

SET = SET PRAM ONLY parameters

ALL = ALL PRAM parameters

*

4: degF and degR can be selected only when optional code /D2 is specified.

*

5: This parameter will not be printed at PRINTOUT upon UPLOAD/DOWNLOAD, although the parameter itself is UPLOADED/DOWNLOADED.

*1

*2

*3

Sensor2

*5