Burn Out Function

(a) Sensor burn out

Configure the burn out mode in the case of sensor
failure or disconnection. When the sensor failure is
detected, the transmitter will output one of the follow-
ing values.

F40: BURN OUT

Select from the followings:

LOW

: Outputs 3.6 mA (-2.5%)

HIGH

: Outputs 21.6 mA (110%)

USER mA

: Output user set value in mA.
Settable 3.6 to 21.6 mA in F41

USER %

: Output user set value in %.
Settable -2.5 to 110 % in F41

OFF

: The burn out output is NOT
defined

F41: BURN OUT VAL

When “USER mA” or “USER %” is selected at
F40:BURN OUT, F41:BURN OUT VAL is displayed.
The output value setting range is 3.6 to 21.6 mA (-2.5
to 110%).

ESC

SET
F40:BURN OUT
HIGH
<HIGH >
<USER mA >
<USER % >
<OFF >

DIAG

PRNT

ESC

PARAM
F40:BURN OUT
USER mA
F41:BURN OUT VAL
21.6 mA
F50:TX FAILURE
HIGH

DEL

CLR

ESC

SET
F41:BURN OUT VAL
21.6 mA
+ 20.8

DIAG

PRNT

ESC

PARAM
F40:BURN OUT
HIGH
F50:TX FAILURE
HIGH
F60:SELF CHECK
GOOD

DATA

DATA

F0307.EPS

Example: Setting output to 20.8 mA in the event of

sensor burn out

1. Select F40: BURN OUT and

press [ENTER].

2. Select "USER mA" and press

[ENTER] twice.

3. Press [OK].

4. Select F40: BURN OUT VAL

and press [ENTER].

5. Set “20.8” and press [ENTER]

twice.

6. Press [OK].

During sensor burn out time, the Sensor1 failure or the
Sensor2 failure error message is generated. (See
Section 4.1.1 for details.)

If the transmitter is equipped with the integral indica-
tor, the LCD displays “Abn.” and “OUT” as shown in
Figure 3.2.

F0308.EPS

Displays "Abn."

Displays "OUT."

Figure 3.2

Integral Indicator Display in Sensor Burn Out

(b) Confirming the output direction if Hard-

ware error occurs

F50: TX FAILURE

The output status of the transmitter in hardware failure
is set by using a jumper on the CPU assembly. (See IM
01C50B01-01E section 3.2) The current setting can be
checked in parameter D50: TX FAILURE.

HIGH

: When an error occurs,

110%(21.6mA) or higher is
output.

LOW

: When an error occurs,

-5%(3.2mA) or lower is output.

3.2.10 Reverse Output Function

H10: REVERSE OUT

To reverse the direction for a 4 to 20 mA DC output
relative to input.

3.2.11 Sensor Backup Function

(For Model YTA320)

IMPORTANT

To use sensor backup function, the following
conditions must be met.

• “Sensor1” is mapped as the PV at B10: PV is.
• “Sensor2” is mapped as the SV at B20: SV is.
• “Sensor1” and “Sensor2” are both correct

input status.

• “HIGH, LOW, User mA, or User %” is se-

lected in the sensor burnout
parameter setting at F40: BURN OUT

The sensor backup command sets the transmitter to
automatically use Sensor2 as PV if Sensor1 fails.
When the transmitter is in the Sensor Backup operation
and switches to Sensor2, there will be no disruption in
the 4 to 20 mA output. The error code for Sensor1
failure is shown on the integral indicator, and also the
error message is sent to the BT200 that the Sensor1
failed and the sensor backup has been in operation. In
case Sensor2 fails during the backup operation, the