Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 28

Advertising
background image

IM 01C50T03-01E

5-2

5. LIST OF PARAMETERS

E

SET SENSOR2

Set Sensor2

R

E10

SENSOR2 TYPE

Sensor2 sensor type

W

TYPE B, E, J, K, L, N, R, S, T, U, W3, W5,
Pt100, Pt200, Pt500, JPt100, Ni120, Cu,
ohm, mV, Non Connection

E20

SENSOR2 WIRE

Sensor2 wire connection

W

2 WIRE, 3 WIRE

E40

SENSOR2 TEMP

Sensor2 input value

R

Unit specified in E20

E41

SENSOR2 UNIT

Sensor2 engineering unit

W

degC, kelvin, degF

*4

, degR

*4

E50

SNSR2 MATCH

Sensor1 RTD sensor matching

W

DISABLE, ENABLE

E51

SNSR2 R0

Sensor1-specific constant (R0)

W

E52

SNSR2 A

IEC co-efficient

W

E53

SNSR2 B

IEC co-efficient

W

E54

SNSR2 C

IEC co-efficient

W

E55

SNSR2 ALPHA

Callendar-Van-Dusen co-efficient A

W

E56

SNSR2 DELTA

Callendar-Van-Dusen co-efficient B

W

E57

SNSR2 BETA

Callendar-Van-Dusen co-efficient C

W

E60

SELF CHECK

Self-diagnostics

R

Same as A60

F

SET OUTPUT

Set output

R

F10

LRV

Lower range value

W

-5000 to +5000

°

C

F20

URV

Upper range value

W

-5000 to +5000

°

C

F30

AUTO LRV

Automatic setting of lower range value

W

DISABLE, ENABLE(-5000 to +5000

°

C)

F35

AUTO URV

Automatic setting of upper range value

W

DISABLE, ENABLE(-5000 to +5000

°

C)

F40

BURN OUT

Sensor error burn-out output

W

LOW, HIGH, USER mA, USER %, OFF

F41

BURN OUT VAL

Sensor error burn-out value

W

3.6 to 21.6mA (-2.5 to 110%)

F50

TX FAILURE

Hardware error burn-out

R

LOW, HIGH

F60

SELF CHECK

Self-diagnostics

R

Same as A60

G

FORCED OUT

Forced output

R

G10

OUTPUT MODE

Output mode

W

AUTOMATIC MODE, MANUAL MODE mA,
MANUAL MODE %

G20

OUTPUT VALUE

Forced output value

W

3.6 to 21.6mA (-2.5 to 110%)

G60

SELF CHECK

Self-diagnostics

R

Same as A60

H

SET MODE

Set Modes

R

H01

CJC SELECT

CJC Selection

W

Internal CJC, Constant CJC

H02

CNST CJC TMP

Constant for CJC function

W

-5000 to +5000

°

C

H10

REVERSE OUT

Reverse output

W

DISABLE, ENABLE

H20

SNSR BACKUP

Sensor backup

W

DISABLE, ENABLE

H21

RETURN SNS1

Return Sensor1

W

ENABLE, DISABLE

H30

UPLOAD SELCT

Upload parameter select

W

SET PRAM ONLY, ALL PRAM

H40

WRITE PROTCT

Write protect

W

YES, NO

H50

WARNING ENBL

Warning function

W

00000000, 3F1C0000, C0030800, FF1F0800,
00E00108, 3FFC0108, C0E30908, FFFF0908

H60

SELF CHECK

Self-diagnostics

R

Same as A60

I

INFORMATION

Information

R

I10

PV LRL

PV lower range limit

R

I11

PV URL

PV upper range limit

R

I12

PV MIN SPAN

PV minimum span

R

I20

SNSR1 LSL

Sensor1 lower sensor limit

R

I21

SNSR1 USL

Sensor1 upper sensor limit

R

I30

SNSR2 LSL

Sensor2 lower sensor limit

R

I31

SNSR2 USL

Sensor2 upper sensor limit

R

I40

TERM LSL

Terminal lower sensor limit

R

I41

TERM USL

Terminal upper sensor limit

R

I59

WARNING

Warning

R

GOOD/Warning, LRV Low Limited, LRV Upp
Limited, URV Low Limited, URV Upp Limited,
LRV>=URV set, SPAN Below, Sns1 TEMP
Little, Sns1 TEMP Large, Sns2 TEMP Little,
Sns2 TEMP Large, Illegal SV MAP, Illegal TV
MAP, Illegal 4V MAP, Out Reverse Mode,
Out Manual Mode

I60

SELF CHECK

Self-diagnostics

R

Same as A60

Pt100

3 WIRE

Operation

degC

DISABLE

+100

+3.9083 E-3

-5.7749 E-7

-4.183 E-12

+3.8505 E-3

+1.4998 E0

+1.0862 E-1

GOOD

+0(degC)

+100(degC)

DISABLE

DISABLE

High

110(%)

High

GOOD

AUTOMATIC MODE

Operation

GOOD

Internal CJC

0

DISABLE

DISABLE

DISABLE

SET PRAM ONLY

NO

00000000

GOOD

-200(degC)

+850(degC)

+25(degC)

-200(degC)

+850(degC)

-200(degC)

+850(degC)

-40(degC)

+85(degC)

GOOD

GOOD

NO.

Parameter name

Content

R/W

Remarks

Applicable model

UPLOAD DATA

110 310 320 SET ALL

Data initial value

YTA110 YTA310 YTA320

*1

*2

*3

*

1:

indicates parameters which may be displayed depending on the setting for other parameters.

indicates parameters available on the model with optional code /CM1.

*

2: RW: R = Read only, W = Read & Write

*

3: Indicates the parameter selected by H30: UPLOAD SELCT.

SET = SET PRAM ONLY parameters
ALL = ALL PRAM parameters

*

4: degF and degR can be selected only when optional code /D2 is specified.