3. OPERATION

Memo

O10: MEMO1, O20: MEMO2

Up to sixteen alphanumeric characters can be entered.

Description

O30: DESCRIPTOR

Up to sixteen alphanumeric characters can be entered.

Date

O40: DATE

Six numeric values can be entered. Only a date
recording function is provided; no internal clock
function is provided, thus the date is not updated.

3.2.7

Forced Output Function

G10: OUTPUT MODE, G20: OUPUT VALUE

This feature can be used to output a fixed current from
3.6 mA (-2.5%) to 21.6 mA (110%) for loop checks.

F0305.EPS

DATA

DIAG

PRNT

ESC

PARAM
G10:OUTPUT MODE
AUTOMATIC MODE
G60:SELF CHECK
GOOD

DATA

DIAG

PRNT

ESC

PARAM
G10:OUTPUT MODE
MANUAL MODE mA
G20:OUTPUT VALUE
4 mA
C60:SELF CHECK
GOOD

DEL

CLR

ESC

SET
G20:OUTPUT VALUE
4 mA
+ 16

FEED

NO

OK

SET
G20:OUTPUT VALUE
16 mA

ESC

SET
G10:OUTPUT MODE
AUTOMATIC MODE
<AUTOMATIC MODE >
<MANUAL MODE mA >
<MANUAL MODE % >

"F.O." lit on.

Example: Outputting 16 mA (75%) constant current

1. Select G10: OUTPUT MODE

and press [ENTER].

2. Set "MANUAL MODE mA."

3. G20: OUTPUT VALUE is

displayed.

Select G20: OUTPUT VALUE

and press [ENTER].

4. Set "16."
5. Pressing [ENTER] twice outputs

a constant current.

If the transmitter is equipped

with the integral indicator, the
LCD displays F.O.

6. Press [OK].

IMPORTANT

• Manual mode output is held for approximately

10 minutes and then released automatically
after the time has elapsed. Even if the BT200
power supply is turned off or the communica-
tion connector is disconnected during the test,
it is held for approximately 10 minutes.

• To release the test output immediately, set

“AUTOMATIC MODE” at G10 as seen in the
figure above or turn off the transmitter.

3.2.8

Integral Indicator Display Function

If the transmitter is equipped with the integral indica-
tor, the following items can be displayed in parameter
settings.

(a) Display process variable

M10: PROCESS DISP

Used to select the process variable
to be displayed on the LCD
indicator. If more than one process
is selected, they are displayed in
sequence as the display update
cycles. The appropriate unit is also
displayed for each process variable.

Also, if the output value is selected at M20, the process
variable and output value are displayed alternately.

PV

: Displays PV value

SV

: Displays SV value

TV

: Displays TV value

4V

: Displays 4V value

PV, SV

: Displays PV and SV
value alternately

PV, SV, TV

: Displays PV, SV and TV
value alternately

PV, SV, TV, 4V

: Displays PV, SV, TV, and
4V value alternately

INHIBIT

: The process variable is
not displayed.

(b) Display output value

M20: %/mA DISP

Used to select the output indica-
tions to be displayed on the LCD
indicator. If two output indications
are selected, they are displayed in
sequence as the display update
cycles.

F03291

Displays PV value.

F03292

Displays output value.