C5. wiring, C5.1 power supply cable connection, C5.1 – Yokogawa YFGW510 User Manual

Page 33: C5-1

Advertising
background image

<C5. Wiring>

C5-1

IM 01W02E01-01EN

C5. Wiring

This chapter describes connection of the power supply cable, grounding cable and network cable

to the installed YFGW510, mounting of antennas and cable connection.

• Use cables with a 70°C rating or higher for explosion-proof devices.
• Explosion-proof device must be wired in compliance with related laws and regulations.

C5.1 Power Supply Cable Connection

This section describes power supply cable wiring.
l

Wiring

Pull the power supply cable into the device through the power cable ground. Connect the power

supply cable to the power supply terminal in the device.
l

Recommended power supply capacity

Output voltage range: 12 to 24V DC (Supplied from power supply to YFGW510)
Output capacity:

10 W or more *

* When starting up YFGW510, an inrush current flows as described in C2.1 Power Supply. Make sure that the power source has current

output capacity at least three times normal current consumption and enough to withstand the inrush current as described below.

l

Inrush current

When power is turned on, an input current flows, which is higher than its normal state. See C2.1

Power Supply about inrush current. Ensure that the power supply and protective devices can

withstand this current.
l

Cable (Insulated for industrial equipment)

Examples

• 600 V polyvinyl chloride insulated wires (IV): JIS C3307
• Polyvinyl chloride insulated wires for electrical apparatus (KIV): JIS C3316
• 600 V grade heat-resistant polyvinyl chloride insulated wires (HIV): JIS C3317
• Heatproof vinyl insulated wires VW-1 (UL1015/UL1007)

Wire size

• Core: AWG14 to 13 (2 to 2.6 mm

2

)

Terminal treatment

• Ring terminal for M4: With insulation covers