F2. status indication and responsive measures, F2-1, Nyfgw510 operational status indication – Yokogawa YFGW510 User Manual

Page 77: Ncommunication status indication, N[lan] led

Advertising
background image

<F2. Status Indication and Responsive Measures>

F2-1

IM 01W02E01-01EN

F2. Status Indication and Responsive

Measures

There are six status indicator LEDs installed on the front of YFGW510: [ACT], [LAN], [ISA],

[WLAN-C1], [WLAN-C2] and [WLAN-AP].

n

YFGW510 operational status indication

The following is the LED that indicates the YFGW510 operational status.

LED

Power off Starting up Connect-

ing

Normal

Mainte-

nance

Abnormal

ACT

OFF

Orange

Orange

blink

Green

Red blink

Red

The LED blinks red when the device mode is changed to Edit mode via the infrared adapter using

the setup tool to configure YFGW510.
If the LED lights red, check the field wireless backbone network cable connection and commu-

nication devices such as the Layer 2 switch, etc., and fix any abnormalities. If there is no abnor-

mality found in cable connection, check the backbone router status information described in F1.

Status Information and device information by the Monitor. Any abnormality found may indicate

the breakdown of YFGW510. For details of the YFGW510 device replacement method, see the

YFGW410 User’s Manual (IM 01W02D01-01EN).

n

Communication status indication

The following are the LEDs that indicate communication status.

LED

Power off Starting

up

Signal

search

Link

down

Link up

Commu-

nicating

Mainte-

nance

Abnor-

mal

LAN

OFF

OFF

N/A

OFF

Green

Green

blink

OFF

Red

ISA

OFF

OFF

N/A

N/A

Green

Green

blink

OFF

Red

WLAN-C1

OFF

OFF

Orange

blink

OFF

Green

blink

Green

OFF

Red

WLAN-C2

OFF

OFF

Orange

blink

OFF

Green

blink

Green

OFF

Red

WLAN-AP

n

[LAN] LED

If the LED turns off during operation, it may indicate that communication between YFGW510 and

the YFGW410 field wireless backbone network has been terminated. Investigate the commu-

nication cable connection and the status of communication devices such as the Layer 2 switch,

etc., and re-establish communication.
If the LED lights red, it may indicate the breakdown of the communication function of YFGW510.

Replace the main body or consult with Yokogawa Electric Corporation.

Advertising