PART-F. TROUBLESHOOTING

This part describes troubleshooting for YFGW510. If any abnormalities are identified in

YFGW510 through investigation and in accordance with procedures described in the YFGW410

User’s Manual (IM 01W02D01-01EN), check the following.

F1. Status Information

The YFGW510 operational status information is shown in the backbone router status (BBR_STA-

TUS) in the Modbus register.

The status data structure and the contents are as follows.

Modbus Address

Name

Data Format

Contents

n

Data

status

Unsigned 16

0x0080, fixed: normal

n + 1

Backbone

router

status

Unsigned 16

Backbone router status (0: connected/1: not

connected)

n + 2 to n + 8

Unsigned 16

0, fixed (reserved bits)

Only the status having a Modbus address of (n + 1) is used. This indicates whether YFGW510 is

connected to YFGW410 correctly.