<C5. Wiring>

C5-11

IM 01W02E01-01EN

l

Grounding cable (Insulated for industrial equipment)

Examples

• 600 V polyvinyl chloride insulated wires (IV): JIS C3307
• Polyvinyl chloride insulated wires for electrical apparatus (KIV): JIS C3316
• 600 V grade heat-resistant polyvinyl chloride insulated wires (HIV): JIS C3317
• Heatproof vinyl insulated wires VW-1 (UL1015/UL1007)

Wire size

• Core: AWA14 to 13 (2 to 2.6 mm

2

)

Terminal treatment

• Ring terminal for M4: With insulation covers

FC0509.ai

ISA100.11a antenna

YFGW510

Antenna extension cable

Grounding cable wiring

Arrestor

Antenna extension cable

Figure C5-9 Wiring for arrestor