C5-11 – Yokogawa YFGW510 User Manual
Page 43
Advertising
<C5. Wiring>
C5-11
IM 01W02E01-01EN
l
Grounding cable (Insulated for industrial equipment)
Examples
• 600 V polyvinyl chloride insulated wires (IV): JIS C3307
• Polyvinyl chloride insulated wires for electrical apparatus (KIV): JIS C3316
• 600 V grade heat-resistant polyvinyl chloride insulated wires (HIV): JIS C3317
• Heatproof vinyl insulated wires VW-1 (UL1015/UL1007)
Wire size
• Core: AWA14 to 13 (2 to 2.6 mm
2
)
Terminal treatment
• Ring terminal for M4: With insulation covers
FC0509.ai
ISA100.11a antenna
YFGW510
Antenna extension cable
Grounding cable wiring
Arrestor
Antenna extension cable
Figure C5-9 Wiring for arrestor