Input type and measurable range, Characters that can be used for units – Yokogawa µR10000 User Manual

Page 38

Advertising
background image

38

IM 04P01B01-02E

Explanation

Note

If the range is changed after setting the alarm, the alarm setting becomes invalid. When you
change the range, check the alarm setting.

In step 5 of setup examples (1), (2), and (3), you can select an input type or a
computation type on the table below.

Mode

Description

TC

Thermocouple

RTD

Resistance temperature detector

Volt

DC voltage

DI

ON/OFF input

1-5V

1-5VDC: 1-5V is scaled to values in the appropriate unit to be used as measured

values. Also, the low-cut function (input less than 0% is fixed to 0% value) can be

used.

Delta

The value obtained by subtracting the measured value of another channel (called

the reference channel) from the input value of the channel set to delta computation is

used as the measured value of that channel.

Scale

The input values are scaled to values in the appropriate unit to be used as measured

values.

SQRT

The square root of the input value is calculated, the result is scaled to a value in the

appropriate unit, and used as the measured value of the channel. Also, the low-cut

function (input less than a given measured value is fixed to 0) can be used.

Skip

Disables measurement, display, periodic printout, and trend recording (dot model).

• Input Type and Measurable Range

Thermocouple (Mode: TC)

RTD (Mode: RTD)

Range Type

Measurable Range

Range Type

Measurable Range

R

0.0 to 1760.0°C

PT(Pt100)

–200.0 to 600.0°C

S

0.0 to 1760.0°C

JPT(JPt100)

–200.0 to 550.0°C

B

0.0 to 1820.0°C

K

–200.0 to 1370.0°C

DC voltage (Mode: Volt)

E

–200.0 to 800.0°C

Range Type

Measurable Range

J

–200.0 to 1100.0°C

20mV

–20.00 to 20.00 mV

T

–200.0 to 400.0°C

60mV

–60.00 to 60.00 mV

N

0.0 to 1300.0°C

200mV

–200.0 to 200.0 mV

W

0.0 to 2315.0°C

2V

–2.000 to 2.000 V

L

–200.0 to 900.0°C

6V

–6.000 to 6.000 V

U

–200.0 to 400.0°C

20V

–20.00 to 20.00 V

WRe

0.0 to 2400.0°C

50V

–50.00 to 50.00 V

ON/OFF input (Mode: DI)

Range Type

Measurable Range

Level

0 to 1

Cont

0 to 1

Characters That Can Be Used for Units

A unit is set using up to six characters.
The available characters are as follows:
Alphabet, numbers, symbols (%, #, °, @, +, –, *, /, (, ), µ, Ω,

2

,

3

, .), and space

Setting the Input Range and Alarm on Measurement Channels